Carrier GT-G 사용자 설명서

다운로드
페이지 56
GT-GS
8
Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05
Application Flexibility
•  Eight Capacities 018, 024, 030, 036, 042, 048, 
and 060.
•  Voltage availability in 208-230/60/1. 
•  Stackable cabinets.
•  Extended range operation (20-120°F EWT) and 
fl ow rates as low as 1.5 gpm per ton.
•  Circuit breaker protected loop and hot water 
gen er a tor pumps.
•  Field selectable low temperature cut-out selection 
setting for well or loop.
•  Corner located electrical box for wiring access 
from two sides.
•  Compressor mounting springs “matched” to each 
compressor for maximum quietness.
•  Narrow cabinet for movement through doorways.
•  Precharged refrigerant circuit with backseating 
service valves for quick installation.
Operating Effi ciencies
•  ARI/ASHRAE/ISO 13256-1 ratings for heating 
COP’s, cooling EER’s and low water fl ow rates.
•  Operating and temperature range allow 
shorter loops.
•  Optional hot water generator with internal pump 
generates hot water at considerable savings.
•  Rugged, super quiet, and highly effi cient 
scroll compressors.
•  Oversized coaxial tube water to refrigerant heat 
exchangers operate at low liquid pressure drop.
•  Convoluted copper (and optional cupronickel) 
water tube functions effi ciently at low-fl ow rates 
and provides freeze-damage resistance.
Service Advantages
•  Removable panels-3 for compressor.
•  Brass swivel-type water and HWG connections 
for quick connection and elimination of wrenches 
or sealants during installation.
•  Solid state digital compressor module provides 
reliable lockout, diagnostic, and time delay functions.
•  High side loss-of-charge sensing reduces nuisance 
low pressure faults.
•  LED Fault and status indication with memory for 
easy diagnostics.
•  Designed for front-access service in tight ap pli ca tions.
•  High and low pressure service ports in the 
refrigerant circuit.
•  Refrigerant sensing freeze protection for more 
accurate low temperature cut-out.
Factory Quality
•  All units are built on our Integrated Process 
Control Assembly System (IPCS). The IPCS is 
a unique state of the art manufacturing system 
that is designed to assure quality of the highest 
standards of any manufacturer in the water-source 
industry. Our IPCS system:
 - 
Verifi es that the correct components are 
  being assembled.
  - Automatically performs special leak tests on 
  all joints.
  - Conducts pressure tests.
  - Performs highly detailed run test unparalleled in  
  the HVAC industry.
 - 
Automatically disables packaging for a “failed” unit.
  - Creates computer database for future service  
  analysis and diagnostics from run test results.
•  Heavy gauge galvanized steel cabinets are epoxy 
powder coated for durable and long-lasting fi nish.
•  All refrigerant brazing is done in a nitrogen 
atmosphere.
•  All units are deep evacuated to less than 100 
microns prior to refrigerant charging.
•  All joints are both helium and halogen leak tested 
to insure annual leak rate of less than 1/4 ounce.
•  Coaxial heat exchanger, refrigerant suction lines 
and all water lines are fully insulated to eliminate 
condensation problems in low temperature 
applications.
•  Noise Reduction features include: double isolation 
mounted compressors, compressor springs, 
insulated compressor compartment, and interior 
cabinet insulation using 1/2” coated glass fi ber.
•  Safety features include: high pressure and loss of 
charge to protect the compressor; condensate 
overfl ow protection; low water temperature 
limit sensors to safeguard the coaxial heat 
exchanger and air coil; hot water high limit and low 
compressor discharge temperature switch provided 
to shut down the hot water generator when 
conditions dictate. Fault lockout enables emergency 
heat
 
and prevents compressor operation until 