Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05
GT-GS Indoor Split (50YCS) Series
General
The liquid source heating/cooling split con dens ing units 
shall be ARI/ASHRAE/ISO 13256-1 loop per for mance 
certifi ed and listed by a nationally recognized safety-
testing laboratory or agency, such as Un der writ er’s 
Lab o ra to ry (UL), or Canadian Stan dards Association 
(CSA-US). Each unit shall be water run-tested at the 
factory. Each unit shall be pallet mounted and shipped in 
clear shrink wrap  for visual shipping damage inspection. 
The units shall be war rant ed by the man u fac tur er against 
defects in materials and workmanship for a period of fi ve 
years on all parts, and ten years on the compressor and 
refrigerant circuit parts with a service labor allowance 
during the fi rst 30 days. An optional extended war ran ty 
is available for the GT-GS Split Series units, which adds 
a labor allowance and trip charge. The liquid source 
units shall be designed to operate with entering liquid 
temperature between 20°F and 120°F.
Casing & Cabinet
The cabinet shall be designed for indoor installations. 
The cabinet shall be fabricated from heavy-gauge 
galvanized steel painted with a epoxy powder coat 
paint with a 1000 hr. salt spray test rating. The interior 
shall be insulated with 1/2" thick, multi-density, coated 
glass fi ber with edges sealed or tucked under fl anges. 
Three compressor com part ment access panels shall 
be provided and shall be removable with linesets and 
water piping in place. The internal com po nent layout 
shall provide for major service with the unit in-place for 
restricted access installations.
Refrigerant Circuit 
All units shall contain split refrigerant circuits employing 
a hermetically sealed com pres sor, thermal expansion 
valve, reversing valve, coaxial tube water-to-refrigerant 
heat exchanger, service ports, and backseating service 
valves. Compressors shall be high-effi ciency advanced 
scroll type designed for heat pump duty and mounted 
on spring vibration isolators. Compressor motors 
shall be single phase PSC with internal overload 
pro tec tion. A factory installed bidirectional fi lter drier 
shall be provided. The coaxial water-to-refrigerant 
heat exchanger shall be designed for close approach 
temperatures and be con struct ed of a convoluted copper 
(optional cupronickel) inner tube and a steel outer 
tube. The thermal expansion valve shall provide proper 
superheat over the entire liquid temperature range with 
min i mal “hunting”. The valve shall operate only in the 
heating mode with the use of an internal check valve. 
The water-to-refrigerant heat exchanger and refrigerant 
suction lines shall be insulated to prevent condensation 
at low liquid temperatures. Air coil con nec tions shall be 
made through brass backseating service valves with 
built-in Schrader ports.
Electrical
CXM Control - A microprocessor-based compressor 
controller (CXM) shall be provided to monitor and control 
unit operation. The control shall provide high and low 
pressure monitoring, fi eld selectable water and air coil 
low water temperature sensing, over/under voltage 
monitoring, and unit performance sentinel (UPS). The 
control shall also provide for water valve connection, a 
test mode, short cycle protection, random start-up, as 
well as fault LED, fault mem o ry, and intelligent fault retry.
The control shall employ quick attach harness 
as sem blies for low voltage connections to the control 
board to aid in troubleshooting or replacement. An 
integral terminal block with screw ter mi nals shall 
be provided on the control for all fi eld low voltage 
connections. Line voltage lugs shall be provided for unit 
wiring. Units shall have knockouts for entrance of low 
and line voltage wiring. The control box shall be harness 
plug-connected for easy removal.
Piping
Supply and return water connections shall be 1" swivel 
fi ttings. All water piping shall be insulated to prevent 
con den sa tion at low liquid temperatures.