INSPECT UNIT — To prepare the unit for installation, com-
plete the procedures listed below:
1. Compare the electrical data on the unit nameplate with
ordering and shipping information to verify that the
correct unit has been shipped.
2. Verify that the unit is the correct model for the entering
water temperature of the job.
3. Do not remove the packaging until the unit is ready for
installation.
4. Verify that the refrigerant tubing is free of kinks or dents,
and that it does not touch other unit components.
5. Inspect all electrical connections. Be sure connections are
clean and tight at the terminals. 
6. Compressors are internally spring-mounted. Compressors
equipped with external spring vibration isolators must
have bolts loosened and shipping clamps removed.
7. Remove any blower support cardboard from inlet of the
blower if present.
8. Locate and verify any accessory kit located in compressor
section.
9. Remove any access panel screws that may be difficult to
remove once unit is installed.
Step 3 — Locate Unit — 
The following guidelines
should be considered when choosing a location for WSHP. Re-
fer to Fig. 1-3 for unit dimensional data. See Fig. 4 for accesso-
ry roof curb dimensional data.
• Provide sufficient space for water, electrical and duct
connections
• Locate unit in an area that allows for easy access and
removal of filter and access panels
• Allow enough space for service personnel to perform
maintenance
Table 1 — Physical Data — Aquazone™ 50RTP03-20 Units
IPT — Iron (National) Pipe Thread
CAUTION
DO NOT store or install units in corrosive environments or
in locations subject to temperature or humidity extremes
(e.g., attics, garages, rooftops, etc.). Corrosive conditions
and high temperature or humidity can significantly reduce
performance, reliability, and service life. Always move
units in an upright position. Tilting units on their sides may
cause equipment damage.
UNIT 50RTP
03
04
05
06
08
10
12
14
20
Compressor (qty)
Scroll (1)
Scroll (2)
Factory Charge R-410A (oz)
64
84
120
132
108
120
130
192
300
Blower Motor
   Motor Quantity
1
   Standard Motor (hp)
1
1
1
1.5
2
3
3
3
5
   Large Motor (hp)
N/A
1.5
1.5
2
3
5
5
5
7.5
Blower(s)
   Number of Blowers
1
2
   Blower Wheel Size (dia x w) 
10 x 6
2 x 12
15 x 11
15 x 15
15 x 11
   V-belt size, Std drive
A29
A30
A32
AX33
B40
BX42
BX46
B39
BX40
Water Connection Size
   IPT (in.)
3
/
4
1
1
1
/
4
1
1
/
2
2
Coax Volume
   Volume (US Gallons)
0.61
0.77
1.11
1.30
1.69
2.29
2.68
3.83
4.77
Condensate Connection Size
   FPT (in.)
1
Air Coil Data
   Air Coil Total Face Area (sq ft)
5
7
9.33
10.5
20
Filter, Standard, Qty...Size (in.)
4...16 x 20
6...16 x 20
8...16 x 20,
2...20 x 20
Operating Weight (lb)
735
785
835
880
1080
1125
1175
1770
1960
Shipping Weight (lb)
750
800
850
900
1100
1150
1200
1800
2000
Corner Weights (lb) 
   Front-Left
184
 196
208.5
224
292
303.5
320
479
530
   Front-Right
259
276
293.5
298
380
395.5
406
623
690
   Rear-Left
108.5
117
124.5
134
193
202
212.5
315
350
   Rear-Right
183.5
 196
208.5
224
215
 224
236.5
353
390
Curb, Installed (lb)
83
94
128