Friedrich H)A12K25L 사용자 설명서

다운로드
페이지 45
26
Reversing Valve in Heating Mode  
When  sluggish  or  stuck  in  the  mid-position,  part  of  the 
discharge gas from the compressor is directed back to the 
suction side, resulting in excessively high suction pressure. 
 
Should  the  valve  fail  to  shift  from  coooling  to  heating, 
block the air flow through the outdoor coil and allow the 
discharge pressure to build in the system. Then switch the 
system from heating to cooling.
If the valve is stuck in the heating position, block the air 
flow through the indoor coil and allow discharge pressure 
to build in the system. Then switch the system from heating 
to cooling.
Should the valve fail to shift in either position after increasing 
the discharge pressure, replace the valve.
Dented  or  damaged  valve  body  or  capillary  tubes  can 
prevent the main slide in the valve body from shifting.
If you determing this is the problem, replace the reversing 
valve.
After all of the previous inspections and checks have been 
made  and  determined  correct,  then  perform  the  “Touch 
Test” on the reversing valve. 
Reversing Valve in Cooling Mode  
Procedure For Changing Reversing Valve 
1.     Install Process Tubes. Recover refrigerant from sealed 
 system. PROPER HANDLING OF RECOVERED 
 REFRIGERANT ACCORDING TO EPA REGULATIONS 
 IS REQUIRED. 
2.      Remove  solenoid  coil  from  reversing  valve.  If  coil  is  to 
 be reused, protect from heat while changing valve. 
3.     Unbraze all lines from reversing valve.
4.      Clean  all  excess  braze  from  all  tubing  so  that  they  will 
 slip into fittings on new valve. 
5.    Remove solenoid coil from new valve.  
The  use  of  a  torch  requires  extreme  care  and  proper 
judgment.  Follow  all  safety  recommended  precautions 
and  protect  surrounding  areas  with  fire  proof  materials. 
Have a fire extinguisher readily available. Failure to follow 
this  notice  could  result  in  moderate  to  serious  property 
damage.
NOTICE
FIRE HAZARD 
Touch Test in heating/Cooling Cycle 
 
 
 
 
The only definite indications that the slide is in the mid-
position is if all three tubes on the suction side of the valve 
are hot after a few minutes of running time. 
NOTE: A condition other than those illustrated above, and  
on Page 31, indicate that the reversing valve is not shifting 
properly. Both tubes shown as hot or cool must be the same 
corresponding temperature. 
Certain unit components operate at 
temperatures hot enough to cause burns.
Proper safety procedures must be followed, 
and proper protective clothing must be 
worn. 
Failure to follow these procedures could 
result in minor to moderate injury.
WARNING
BURN HAZARD 
Sealed Refrigeration System contains refrigerant 
and oil under high pressure.
Proper safety procedures must be followed, 
and proper protective clothing must be worn 
when working with refrigerants.
Failure  to  follow  these  procedures  could 
result in serious injury or death. 
WARNING
HIGH PRESSURE HAZARD