Friedrich WE13B33B-B 사용자 설명서

다운로드
페이지 30
13
 10. 
Evacuate system to maximum absolute holding pres-
sure of 200 microns or less. NOTE:  This process can 
be speeded up by use of heat lamps, or by breaking 
the vacuum with refrigerant or dry nitrogen at 5,000 
microns. Pressure system to 5 PSIG and leave in 
system a minimum of 10 minutes. Release refriger-
ant, and proceed with evacuation of a pressure of 
200 microns or less.
 11. 
Break vacuum by charging system from the high side 
with the correct amount of refrigerant specifi ed. This 
will prevent boiling the oil out of the crankcase.
 
 
NOTE:  If the entire charge will not enter the high 
side, allow the remainder to enter the low side in 
small increments while operating the unit.
 12. 
Restart unit several times after allowing pressures 
to stabilize. Pinch off process tubes, cut and solder 
the ends. Remove pinch off tool, and leak check the 
process tube ends.
SPECIAL PROCEDURE IN THE CASE OF MOTOR
COMPRESSOR BURNOUT
  1. 
Recover all refrigerant and oil from the system.
  2. 
Remove compressor, capillary tube and fi lter drier 
from the system.
  3. 
Flush evaporator condenser and all connecting 
tubing with dry nitrogen or equivalent, to remove 
all contamination from system. Inspect suction and 
discharge line for carbon deposits. Remove and 
clean if necessary.
  4. 
Reassemble the system, including new drier strainer 
and capillary tube.
  5. 
Proceed with processing as outlined under hermetic 
component replacement.
ROTARY COMPRESSOR SPECIAL 
TROUBLESHOOTING AND SERVICE
Basically, troubleshooting and servicing rotary compres-
sors is the same as on the reciprocating compressor with 
only a few exceptions.
  1. 
Because of the spinning motion of the rotary, the 
mounts are critical. If vibration is present, check the 
mounts carefully.
  2. 
The electrical terminals on the rotary are in a differ-
ent order than the reciprocating compressors. The 
terminal markings are on the cover gasket. Use your 
wiring diagram to insure correct connections.
REFRIGERANT CHARGE
  1. 
The refrigerant charge is extremely critical. Mea-
sure charge carefully - as exact as possible to the 
nameplate charge.
  2. 
The correct method for charging the rotary is to 
introduce liquid refrigerant into the high side of the 
system with the unit off. Then start compressor and 
enter the balance of the charge, gas only, into the 
low side.
 
 
The introduction of liquid into the low side, without 
the use of a capillary tube, will cause damage to 
the discharge valve of the rotary compressor.
 
 
NOTE:   All inoperative compressors returned to 
Friedrich must have all lines properly plugged with 
the plugs from the replacement compressor.