Energy Tech Laboratories DSH 사용자 설명서

다운로드
페이지 24
JOHNSON CONTROLS
20
FORM 145.32-IOM1 (908)
Flash code number corresponds to a number of LED 
flashes, followed by a pause and then repeated. 
TRIP and ALERT LED’s flashing at the same time 
means control circuit voltage is too low for opera-
tion. 
Resetting Alert Codes 
Alert codes can be reset manually and automatically. 
The manual method to reset an Alert code is to cycle the 
power to Comfort Alert off and on. For automatic reset, 
Comfort Alert continues to monitor the compressor and 
system after an Alert is detected. If conditions return to 
normal, the Alert code is turned off automatically. ALERT 
codes that result in a compressor lock out can only be 
reset manually. ALERT codes that result in a lockout 
can only be reset manually.
 
Status LED 
Status LED Description 
Status LED Troubleshooting Information 
1. Low line voltage to compressor 
2. Excessive liquid refrigerant in compressor 
3. Compressor bearings are seized 
1. Condensing unit power disconnect is open 
2. Compressor circuit breaker or fuses are open 
3. Compressor contactor has failed open 
4. High pressure switch is open and requires manual reset 
5. Broken supply wires or connector is not making contact 
6. Unusually long compressor protector reset time due to   
extreme ambient temperature 
7. Compressor windings are damaged 
1. Compressor fuse is open on one phase 
2. Broken wire or connector on one phase 
3. Compressor motor winding is damaged 
4. Utility supply has dropped one phase 
Yellow “ALERT” 
Flash Code 7 
Reverse Phase 
LOCKOUT 
1. Compressor running backward due to 
     supply phase reversal 
1. Compressor contactor has failed closed  
2. Thermostat demand signal not connected to module 
1. Control circuit transformer is overloaded 
2. Low line voltage to compressor  
Yellow “ALERT” 
Flash Code 9 
Low Voltage 
Control circuit < 18VAC 
Yellow “ALERT” 
Flash Code 5 
Open Circuit 
Yellow “ALERT” 
Flash Code 8 
Welded Contactor 
Compressor always runs 
Yellow “ALERT” 
Flash Code 6 
Missing Phase 
LOCKOUT 
Locked Rotor 
LOCKOUT 
Yellow “ALERT” 
Flash Code 4