Heat Controller HEV/H 사용자 설명서

다운로드
페이지 46
19
Heat Controller, Inc. 
HEV/H SERIES
 
Installation, Operation & Maintenance
HOT WATER GENERATOR
Insulated water lines - 5/8” OD, 50 ft maximum (one way)
[16mm OD, 15 meters maximum]
Upper element to 130°F [54°C]
(or owner preference)
Cold Inlet
Hot Outlet to
house
Powered
Water Heater
Cold Inlet from
Domestic supply
Hot Outlet
Unpowered
Water Heater
Field Supplied 3/4” brass nipple and “T”
Lower element to 120°F [49°C]
Shut-off
Valve #1
Shut-off
Valve #4
Shut-off
Valve #3
Shut Off 
Valve #2
Hot Outlet
to home
Insulated water lines - 
5/8” OD, 50 ft maximum (one way)
[16mm OD, 15 meters maximum]
Powered
Water
Heater
Upper
element to
120 - 130°F
[49 - 54°C]
Lower
element to
100 - 110°F
[38 - 43°C]
Shut-off
Valve #3
Shut Off 
Valve #2
Field supplied 3/4’ brass nipple and ‘T’
Cold
Inlet
Shut Off 
Valve #4
Shut Off 
Valve #1
 
WARNING! 
WARNING!  A 150°F SETPOINT MAY LEAD TO 
SCALDING OR BURNS.  THE 150°F SET POINT MUST 
ONLY BE USED ON SYSTEMS THAT EMPLOY AN 
APPROVED ANTI-SCALD VALVE.
The HWG (Hot Water Generator) or desuperheater option 
provides considerable operating cost savings by utilizing 
heat energy from the compressor discharge line to help 
satisfy domestic hot water requirements. The HWG is active 
throughout the year, providing virtually free hot water when 
the heat pump operates in the cooling mode or hot water at 
the COP of the heat pump during operation in the heating 
mode.
Heat pumps equipped with the HWG option include a built-
in water to refrigerant heat exchanger that eliminates the 
need to tie into the heat pump refrigerant circuit in the fi eld. 
The control circuit and pump are also built in for residential 
equipment. Figure 14 shows a typical example of HWG water 
piping connections on a unit with built-in circulating pump. 
This piping layout prevents sludge/debris from the bottom of 
the tank being pulled into the HWG pump.
The temperature set point of the HWG is fi eld selectable 
to 125°F or 150°F .  The 150°F  set point allows more heat 
storage from the HWG.  For example, consider the amount 
of heat that can be stored by the HWG when using the 125°F 
set point, versus the amount of heat that can be generated 
by the HWG when using the 150°F set point.
In a typical 50 gallon two-element electric water heater 
the lower element should be turned down to 100°F, or the 
lowest setting, to get the most from the HWG.  The tank will 
eventually stratify so that the lower 80% of the tank, or 40 
gallons, becomes 100°F (controlled by the lower element).  
The upper 20% of the tank, or 10 gallons, will be maintained 
at 125°F (controlled by the upper element).
Using a 125°F set point, the HWG can heat the lower 40 
gallons of water from 100°F to 125°F, providing up to 8,330 
btu’s of heat.  Using the 150°F set point, the HWG can heat 
the same 40 gallons of water from 100°F to 150°F and the 
remaining 10 gallons of water from 125°F to 150°F, providing 
a total of up to 18,743 btu’s of heat, or more than twice as 
much heat as when using the 125°F set point.
Dual element electric water heaters are recommended. 
If a gas, propane, oil or electric water heater with a 
single element is used, a second preheat storage tank 
is recommended to insure a usuable entering water 
temperature for the HWG.
Typically a single tank of at least 50 gallons (189 liters) is used 
to limit installation costs and space. However, a dual tank, as 
shown in Figure 21, is the preferred system, as it provides the 
maximum storage and temperate source water to the HWG.
It is always advisable to use water softening equipment on 
domestic water systems to reduce the scaling potential and 
lengthen equipment life. In extreme water conditions, it may 
be necessary to avoid the use of the HWG option since the 
potential cost of frequent maintenance may offset or exceed 
any savings. Consult Table 3 for scaling potential tests.
Figure 14: Typical HWG Installation
Figure 15: HWG Double Tank Installation