Installation, Operation & Maintenance 
HEV/H SERIES
 
Heat Controller, Inc.
Electrical Data -
ELECTRICAL - LINE VOLTAGE
WARNING!  To avoid possible injury or death 
due to electrical shock, open the power 
supply disconnect switch and secure it in an 
open position during installation.
CAUTION!  Use only copper conductors for field 
installed electrical wiring. Unit terminals are not 
designed to accept other types of conductors.
Electrical - Line Voltage
All field installed wiring, including electrical ground, must 
comply with the National Electrical Code as well as all 
applicable local codes. Refer to the unit electrical data for 
fuse sizes.  Consult wiring diagram for field connections 
that must be made by the installing (or electrical) 
contractor.
All final electrical connections must be made with a 
length of flexible conduit to minimize vibration and sound 
transmission to the building.
General Line Voltage Wiring
Be sure the available power is the same voltage and 
phase shown on the unit serial plate. Line and low voltage 
wiring must be done in accordance with local codes or the 
National Electric Code, whichever is applicable. 
ѥ WARNING! ѥ
ѥ CAUTION! ѥ
HE 
Model
Volt 
Code
Rated Voltage
Voltage 
Min/Max
Compressor
HWG
Pump
FLA
Ext 
Loop 
Pump 
FLA
Fan
Motor
FLA
Total
Unit
FLA
Min
Circuit
Amp
Max
Fuse/
HACR
RLA
LRA
Qty
024
1
208-230/60/1
197/252
11.7
58.3
1
0.5
4.0
3.9
20.1
23.0
30
030
1
208-230/60/1
197/252
13.1
73.0
1
0.5
4.0
3.9
21.5
24.7
35
036 1
208-230/60/1
197/252
15.3
83.0
1
0.5
4.0
3.9
23.7
27.5
40
042
1
208-230/60/1
197/252
17.9
96.0
1
0.5
4.0
5.2
27.6
32.0
45
048
1
208-230/60/1
197/252
21.2
104.0
1
0.5
4.0
5.2
30.9
36.2
50
060
1
208-230/60/1
197/252
27.1
152.9
1
0.5
4.0
6.9
38.5
45.2
70
HACR circuit break in U.S. only 
Wire length based on one way measurement with 2% voltage drop
All fuses Class RK-5 
Wire sizes based on 140°F (60°C) copper conductor