Heat Controller HEV/H 사용자 설명서

다운로드
페이지 46
32
Installation, Operation & Maintenance 
HEV/H SERIES
 
Heat Controller, Inc.
UNIT COMMISSIONING AND OPERATING CONDITIONS
Table 9a: Building Operating Limits
Operating Limits
Environment – Units are designed for indoor installation only. Never install units in areas subject to freezing or where humidity levels 
could cause cabinet condensation (such as unconditioned spaces subject to 100% outside air). 
Power Supply – Voltage utilization shall comply with AHRI standard 110, voltage range A.
Determination of operating limits is dependent primarily upon three factors: 1) return air temperature. 2) water temperature, 
and 3) ambient temperature. When any one of these factors is at minimum or maximum levels, the other two factors should be 
at normal levels to insure proper unit operation. Extreme variations in temperature and humidity and/or corrosive water or air 
will adversely affect unit performance, reliability, and service life. Consult Table 9a for operating limits.
Commissioning Conditions
Consult Table 9b for commissioning conditions. Starting conditions vary depending upon model and are based upon the 
following notes:   
Notes:
1.  Conditions in Table 9b are not normal or continuous operating conditions. Minimum/maximum limits are start-up conditions 
to bring the building space up to occupancy temperatures.  Units are not designed to operate under these conditions on a 
regular basis.
2.   Voltage utilization complies with AHRI Standard 110, voltage range B.
Cooling
Heating
Air Limits
Min. ambient air, DB
45ºF [7ºC]
39ºF [4ºC]
Rated ambient air, DB
80.6ºF [27ºC]
68ºF [20ºC]
Max. ambient air, DB
130ºF [54ºC]
85ºF [29ºC]
Min. entering air, DB/WB
60ºF [16ºC]
40ºF [4.5ºC]
Rated entering air, DB/WB
80.6/66.2ºF [27/19ºC]
68ºF [20ºC]
Max. entering air, DB/WB
110/83ºF [43/28ºC]
80ºF [27ºC]
Water Limits
Min. entering water
20ºF [-6.7ºC]
20ºF [-6.7ºC]
Normal entering water
50-110ºF [10-43ºC]
30-70ºF [-1 to 21ºC]
Max. entering water
120ºF [49ºC]
120ºF [49ºC]
Unit
Commissioning Limits
Normal Water Flow
1.5 to 3.0 gpm / ton
[1.6 to 3.2 l/m per kW]
Rev.: 4 June, 2012
Cooling
Heating
Air Limits
Min. ambient air, DB
45ºF [7ºC]
39ºF [4ºC]
Rated ambient air, DB
80.6ºF [27ºC]
68ºF [20ºC]
Max. ambient air, DB
130ºF [54ºC]
85ºF [29ºC]
Min. entering air, DB/WB
65/45ºF [18/7ºC]
50ºF [10ºC]
Rated entering air, DB/WB
80.6/66.2ºF [27/19ºC]
68ºF [20ºC]
Max. entering air, DB/WB
100/75ºF [38/24ºC]
80ºF [27ºC]
Water Limits
Min. entering water
20ºF [-6.7ºC]
20ºF [-6.7ºC]
Normal entering water
50-110ºF [10-43ºC]
30-70ºF [-1 to 21ºC]
Max. entering water
120ºF [49ºC]
120ºF [49ºC]
Unit
Operating Limits
Normal Water Flow
1.5 to 3.0 gpm / ton
[1.6 to 3.2 l/m per kW]
Rev.: 4 June, 2012
70/50ºF Reheat
Table 9b: Building Commissioning Limits