Heat Controller HEV/H 사용자 설명서

다운로드
페이지 46
40
Installation, Operation & Maintenance 
HEV/H SERIES
 
Heat Controller, Inc.
General
If operational diffi culties are encountered, perform 
the preliminary checks below before referring to the 
troubleshooting charts.
• Verify that the unit is receiving electrical supply power.
• Make sure the fuses in the fused disconnect switches are 
intact.
After completing the preliminary checks described above, 
inspect for other obvious problems such as leaking 
connections, broken or disconnected wires, etc. If everything 
appears to be in order, but the unit still fails to operate 
properly, refer to the “DXM2 Troubleshooting Process
Flowchart” or “Functional Troubleshooting Chart.”
DXM2 Board
DXM2 board troubleshooting in general is best summarized 
as verifying inputs and outputs. After inputs and outputs 
have been verifi ed, board operation is confi rmed and the 
problem must be elsewhere. Below are some general 
guidelines for troubleshooting the DXM2 control.
Field Inputs
Conventional thermostat inputs are 24VAC from the 
thermostat and can be verifi ed using a voltmeter between C 
and Y1, Y2, W, O, G. 24VAC will be present at the terminal 
(for example, between “Y1” and “C”) if the thermostat is 
sending an input to the DXM2 board.
Proper communications with a thermostat can be verifi ed 
using the Fault LED on the DXM2.  If the control is NOT 
in the Test mode and is NOT currently locked out or in 
a retry delay, the Fault LED on the DXM2 will fl ash very 
slowly (1 second on, 5 seconds off), if the DXM2 is properly 
communicating with the thermostat.
Sensor Inputs
All sensor inputs are ‘paired wires’ connecting each 
component to the board. Therefore, continuity on pressure 
switches, for example can be checked at the board 
connector.  The thermistor resistance should be measured 
with the connector removed so that only the impedance of 
the thermistor is measured. If desired, this reading can be 
compared to the thermistor resistance chart shown in the 
DXM2 AOM manual. An ice bath can be used to check the 
calibration of the thermistor.
Outputs
The compressor and reversing valve relays are 24VAC 
and can be verifi ed using a voltmeter.  For units with PSC 
blower motors, the fan relay provides a contact closure to 
directly power the blower motor, or provide 24VAC to an 
external fan relay. For units with ECM blower motors, the 
DXM2 controls the motor using serial communications, 
and troubleshooting should be done with a communicating 
thermostat or diagnostic tool.  The alarm relay can either 
be 24VAC as shipped or dry contacts for use with DDC 
controls by clipping the JW1 jumper. Electric heat outputs 
are 24VDC “ground sinking” and require a voltmeter set for 
DC to verify operation. The terminal marked “24VDC” is the 
24VDC supply to the electric heat board; terminal “EH1” is 
stage 1 electric heat; terminal “EH2” is stage 2 electric heat. 
When electric heat is energized (thermostat is sending a “W” 
input to the DXM2 controller), there will be 24VDC between 
terminal “24VDC” and “EH1” (stage 1 electric heat) and/or 
“EH2” (stage 2 electric heat). A reading of 0VDC between 
“24VDC” and “EH1” or “EH2” will indicate that the DXM2 
board is NOT sending an output signal to the electric heat 
board.
Test Mode
Test mode can be entered for 20 minutes by pressing the 
Test pushbutton. The DXM2 board will automatically exit test 
mode after 20 minutes.
Advanced Diagnostics
If a communicating thermostat or diagnostic tool is 
connected to the DXM2, additional diagnostic information 
and troubleshooting capabilities are available.  The current 
status of all DXM2 inputs can be verifi ed, including the 
current temperature readings of all temperature inputs.  
With a communicating thermostat the current status of the 
inputs can be accessed from the Service Information menu.  
In the manual operating mode, most DXM2 outputs can 
be directly controlled for system troubleshooting.  With a 
communicating thermostat the manual operating mode can 
be accessed from the Installer menu.  For more detailed 
information on the advanced diagnostics of the DXM2, see 
the DXM2 Application, Operation and Maintenance (AOM) 
manual (part #97B0003N15). 
DXM2 Troubleshooting Process Flowchart/Functional 
Troubleshooting Chart
The “DXM2 Functional Troubleshooting Process Flowchart” 
is a quick overview of how to start diagnosing a suspected 
problem, using the fault recognition features of the DXM2 
board. The “Functional Troubleshooting Chart” on the 
following page is a more comprehensive method for 
identifying a number of malfunctions that may occur, and is 
not limited to just the DXM2 controls. Within the chart are 
fi ve columns:
•  The “Fault” column describes the symptoms.
•  Columns 2 and 3 identify in which mode the fault is likely 
to occur, heating or cooling.
•  The “Possible Cause column” identifi es the most likely 
sources of the problem.
•  The “Solution” column describes what should be done to 
correct the problem.
WARNING!
  HAZARDOUS VOLTAGE! DISCONNECT 
ALL ELECTRIC POWER INCLUDING REMOTE 
DISCONNECTS BEFORE SERVICING.
Failure to disconnect power before servicing can cause 
severe personal injury or death.
TROUBLESHOOTING
 
WARNING!