Toshiba RAV-SM1403AT-E1 사용자 설명서

다운로드
페이지 93
– 18 –
*
4 poles are provided to this compressor.
The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.
RAV-SM1103AT-E1
Pressure
Pipe surface temp.
Temp
*
Comp.
*
Comp.
(MPa)
(kg/cm
2
G)
Pd
Ps
Pd
Ps
TD
TS
TC
TL
TE
Hz
Fan
In
Out
Cooling
Standard
3.44
0.92
35.1
9.4
82
8
10
56
39
47
HIGH
27/19
35/–
Overload
3.73
1.18
38.1
12.0
82
15
17
59
48
42
HIGH
32/24
43/–
Low load
1.49
0.70
15.2
7.1
39
8
3
23
22
30
LOW 18/15.5
–5/–
Heating
Standard
2.80
0.61
28.6
6.2
80
0
46
7
1
48
HIGH
20/–
7/6
Overload
3.43
1.08
35.0
11.0
82
14
55
12
13
24
LOW
30/–
24/18
Low load
2.20
0.25
22.4
2.6
76
-19
36
-16
-16
55
HIGH
15/–
–10/(70%)
3.52
0.85
35.9
8.7
87
8
9
57
39
54
HIGH
27/19
35/–
3.78
1.12
38.6
11.4
84
15
17
59
47
45
HIGH
32/24
43/–
1.51
0.71
15.4
7.2
40
7
3
23
23
30
LOW 18/15.5
–5/–
2.88
0.60
29.4
6.1
85
1
47
6
1
61
HIGH
20/–
7/6
3.41
1.08
34.8
11.0
81
14
54
13
13
24
LOW
30/–
24/18
2.35
0.24
24.0
2.4
80
-19
40
-16
-16
73
HIGH
15/–
–10/(70%)
RAV-SM1403AT-E1
Pressure
Pipe surface temp.
Temp
(MPa)
(kg/cm
2
G)
Pd
Ps
Pd
Ps
TD
TS
TC
TL
TE
Hz
Fan
In
Out
Cooling
Standard
Overload
Low load
Heating
Standard
Overload
Low load