4. Single group operation
• Each indoor unit controls the outdoor unit individually.
5. Multiple groups operation (Manual address setting)
• Header unit: The header unit receives the indoor unit data (thermo status) of the follower
(Without identical line address & indoor/outdoor serial) and then finally controls the outdoor
compressor matching with its own thermo status.
The header unit sends this command information to the follower unit.
compressor matching with its own thermo status.
The header unit sends this command information to the follower unit.
• Follower unit: The follower unit receives the indoor unit data from the header (With identical line address &
indoor/outdoor serial) and then performs the thermo operation synchronized with the header
unit. The follower unit sends own thermo ON/OFF demand to the header unit.
unit. The follower unit sends own thermo ON/OFF demand to the header unit.
(Example)
No. 1-1 header unit sends/receives signal to/from No. 1-2 and No. 1-3 follower units.
(It is not influenced by the line 2 or 3 address indoor unit.)
(It is not influenced by the line 2 or 3 address indoor unit.)
2-1
Sub/Header
1-1
Sub/Header
4-1
Master/Header
3-1
Sub/Header
8-1
Sub/Header
2-1
Sub/Header
1-1
Sub/Header
1-2
Sub/Follower
3-1
Master/Header
3-2
Sub/Follower
3-3
Sub/Follower