TABLE 2-14 – ELECTRIC HEAT
TABLE 2-15 – AIRFLOW AND ENTERING AIR/AMBIENT LIMITATIONS
* Cooling Only Units
KW
NOMINAL VOLTAGE
208/3/60
AMPS
230/3/60
AMPS
460/3/60
AMPS
575/3/60
AMPS
40
96
96
48
40
80
193
193
96
80
108
260
260
130
109
150
181
151
Limitations
Model Size
50
51
60
61
Minimum 
Airflow at 
Standard Design 
Conditions. 
CFM*
(min to max)
10000 -
22500
10000 -
22500
12500 -
24000
12500 -
24000
Entering Wet 
Bulb Temp F° 
(min/max)
57/75
57/75
57/75
57/75
Entering Dry 
Bulb Temp F° 
(min/max)
68/90
68/90
68/90
68/90
Ambient Temp F°
without Low 
Amb option
50/120
50/120
50/120
50/120
Ambient Temp F°
with Low Amb 
option
0/120
0/120
0/120
0/120
ELECTRIC DATA (CONTINUED)