1. G4FD coils available with a factory installed horizontal drain pan. See price pages for specific model number.
2. Single phase units require single phase 2HK heaters.
COOLING CAPACITY - With Air Handler Coils
UNIT MODEL
AIR HANDLER
COIL MODEL
1
COOLING
MODEL
ELECTRIC
2
 
HEAT KW
W
RATED 
CFM
NET MBH
SEER
EER
TOTAL
SENS.
1 PH 13 SEER AC WITH MV - VARIABLE SPEED
AY018MA321
MV12B
5,8,10
17
FC/MC18B
600
18.4
12.8
14.50
12.00
MV12B
5,8,10
17
G4FD024H17T2A
600
18.4
12.8
14.50
12.00
AY024MA321
MV12B
5,8,10
17
FC/MC24B
800
24.0
17.7
14.50
12.00
MV12B
5,8,10
17
FC/MC30B
800
24.0
17.7
14.50
12.00
MV12B
5,8,10
17
FC/MC36B
800
24.0
17.7
14.50
12.00
MV12B
5,8,10
17
G4FD030H17T2A
800
24.0
17.7
14.50
12.00
MV12B
5,8,10
17
G4FD036H17T2A
800
24.0
17.7
14.50
12.00
MV16C
5,8,10,15,18,20
21
FC/MC36C
800
24.0
17.7
14.50
12.00
AY030MA321
MV12B
5,8,10
17
FC/MC36B
1000
29.2
21.4
11.70
10.40
MV12B
5,8,10
17
FC/MC42B
1000
29.4
21.6
12.00
10.40
MV12B
5,8,10
17
G4FD036H17T2A
1000
29.2
21.4
11.70
10.40
MV12B
5,8,10
17
G4FD046H17T2A
1000
29.4
21.6
12.00
10.40
MV16C
5,8,10,15,18,20
21
FC/MC36C
1000
29.4
21.6
11.70
10.40
MV16C
5,8,10,15,18,20
21
FC/MC42C
1000
29.4
21.6
11.70
10.40
MV16C
5,8,10,15,18,20
21
G4FD036H21T2A
1000
29.4
21.6
11.70
10.40
MV16C
5,8,10,15,18,20
21
G4FD042H21T2A
1000
29.4
21.6
11.70
10.40
AY036MA321
MV12B
5,8,10
17
FC/MC42B
1200
35.8
25.9
13.75
11.00
MV12B
5,8,10
17
G4FD046H17T2A
1200
35.8
25.9
13.75
11.00
MV16C
5,8,10,15,18,20
21
FC/MC42C
1200
36.0
26.1
14.00
11.50
MV16C
5,8,10,15,18,20
21
FC/MC48C
1200
36.0
26.1
14.00
11.50
MV16C
5,8,10,15,18,20
21
G4FD042H21T2A
1200
36.0
26.1
14.00
11.50
MV16C
5,8,10,15,18,20
21
G4FD048H21T2A
1200
36.0
26.1
14.00
11.50
MV20D
8,10,15,18,20,25
24
FC/MC48D
1200
36.0
26.1
14.00
11.50
MV20D
8,10,15,18,20,25
24
G4FD048H24T2A
1200
36.0
26.1
14.00
11.50
1 PH 13 SEER AC WITH AHP
AY012MA321
AHP18
2,5,8
17
430
15.5
9.9
13.50
11.00
AY018MA321
AHP18
2,5,8
17
650
18.0
12.4
13.00
11.00
AHP24
2,5,8,10
17
655
18.0
12.4
13.00
11.00
AY024MA321
AHP24
2,5,8,10
17
830
23.4
17.1
13.00
11.00
AY030MA321
AHP36
5,8,10,15,18
17
1040
28.8
21.0
10.90
9.90
AY036MA321
AHP42
5,8,10,15,18
21
1255
35.4
25.5
13.00
11.00
1 PH 13 SEER AC WITH F4FP
AY018MA321
F4FP024H06T2A
5,8,10
17
600
18.0
12.4
13.00
11.00
AY024MA321
F4FP030H06T2A
5,8,10,15
17
800
23.4
17.1
13.00
11.00
AY036MA321
F4FP042H06T2A
5,8,10,15
24
1200
35.4
25.5
13.00
11.00
Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210.
Cooling MBH based on 80ºF entering air temperature, 50% RH, and rated air flow.
EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at 95ºF outdoor ambient divided by the total electric power in watt-hours at those conditions
.
SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BUT’s during a normal annual usage period for cooling divided by the total electric power 
input in watt-hours during the same period.