Carrier 50ZH024-060 사용자 설명서

다운로드
페이지 24
mild detergent-and-water-solution. Rinse coils with clear water,
using a garden hose. Be careful not to splash water on motors,
insulation, wiring or air filter(s). For best results, spray outdoor-
coil fins from inside to outside the unit. On units with an outer and
inner outdoor coil, be sure to clean between the coils. Be sure to
flush all dirt and debris from the unit base.
Inspect the drain pan and condensate drain line when inspecting
the coils. Clean the drain pan and condensate drain by removing all
foreign matter from the pan. Flush the pan and drain tube with
clear water. Do not splash water on the insulation, motor, wiring,
or air filter(s). If the drain tube is restricted, clear it with a
‘‘plumbers snake’’ or similar probe device. Ensure that the
auxiliary drain port above the drain tube is also clear.
Step 5—Outdoor Fan
Keep the Outdoor fan free from all obstructions to ensure
proper cooling operation. Never place articles on top of the
unit. Damage to unit may result.
1. Shut off unit power supply and install lockout tag.
2. Remove outdoor-fan assembly (grille, motor, motor cover,
and fan) by removing screws and flipping assembly onto unit
top cover.
3. Loosen fan hub setscrews.
4. Adjust fan height as shown in Fig. 21 or 22.
5. Tighten setscrews.
6. Replace outdoor-fan assembly.
Table 4—Dry Coil Air Delivery* Horizontal Discharge
(Deduct 10 percent for 208 Volt Operation)
230 AND 460 VOLT
Unit
Motor Speed
Watts/CFM
External Static Pressure (in. wg)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
024
Low
Watts
288
285
282
279
274
268
261
-
-
Cfm
875
820
802
734
668
582
478
-
-
Med
Watts
390
383
378
369
360
350
340
-
-
Cfm
1131
1090
1038
978
917
830
721
-
-
High
Watts
528
520
510
495
480
460
450
-
-
Cfm
1391
1338
1285
1200
1115
1018
920
-
-
030
Low
Watts
288
285
282
279
274
268
261
-
-
Cfm
875
820
802
734
668
582
478
-
-
Med
Watts
390
383
378
369
360
350
340
-
-
Cfm
1131
1090
1038
978
917
830
721
-
-
High
Watts
528
520
510
495
480
460
450
-
-
Cfm
1891
1338
1285
1200
1115
1018
920
-
-
036
Low
Watts
450
435
420
400
380
335
326
311
-
Cfm
1231
1218
1204
1120
1008
950
863
751
-
Med
Watts
470
450
445
410
388
359
338
321
-
Cfm
1302
1264
1205
1163
1081
940
873
783
-
High
Watts
660
635
610
575
540
505
485
460
-
Cfm
1700
1660
1581
1450
1297
1190
1095
999
-
042 †
Low
Watts
478
458
440
411
378
350
327
317
-
Cfm
1303
1270
1224
1179
1126
1022
911
816
-
Med
Watts
481
468
450
438
404
370
338
320
-
Cfm
1310
1280
1241
1181
1110
1022
943
811
-
High
Watts
-
798
678
647
618
578
540
500
460
Cfm
-
1736
1688
1618
1510
1421
1309
1187
1060
048 †
Low
Watts
-
-
801
760
730
688
650
600
570
Cfm
-
-
1898
1841
1757
1682
1564
1429
1333
Med
Watts
-
-
-
-
-
-
-
-
-
Cfm
-
-
-
-
-
-
-
-
-
High
Watts
-
-
870
842
818
782
696
632
628
Cfm
-
-
2000
1903
1799
1718
1625
1446
1365
060 †
Low
Watts
890
850
810
790
735
680
580
480
422
Cfm
1834
1820
1791
1762
1703
1640
1415
1159
950
Med
Watts
1040
1018
1000
950
890
835
790
650
580
Cfm
2230
2102
2025
1960
1901
1855
1752
1468
1121
High
Watts
1073
1038
1001
958
896
840
800
691
575
Cfm
2230
2202
2160
2122
2052
1926
1791
1588
1202
† 460-v motors are 2-speed.
Air delivery values are based on operating voltage of 230-v. or 460-v., dry coil, without filter or electric heater. Deduct wet coil, filter, and electric heater pressure drops
to obtain external static pressure availabe for ducting.
Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occur at airflows below
this point.
Dashes indicate portions of the table that are beyond the blower motor capacity or are not recommended.
17