LEGEND
*Shipping weights include base unit plus packaging.
†If components are to be split, additional refrigerant will be needed.
**Two-speed motor.
††Use Type L copper only.
NOTE: If components are to be split, the maximum length of refrigerant tubing to be
used is 50 equivalent ft, assuming components will be installed in same horizontal plane.
If components are not to be installed in same horizontal plane, contact your Carrier rep-
resentative for more information. For additional piping information, refer to Carrier
System Design Manual, Part 3.
UNIT 50AH
024
036
048
060
SHIPPING WEIGHT (lb)*
560
590
690
700
OPERATING WEIGHT (lb)
Base Unit, Evaporator/Condenser Section
450, 193/256
480, 206/274
580, 250/330
590, 254/336
REFRIGERANT TYPE
R-22
Operating Charge (lb)†
5.4
5.5
7.4
7.6
COMPRESSOR — TYPE
Scroll
Quantity...Model
(1)...ZR23
(1)...ZR34
(1)...SR48
(1)...ZR57
Oil (oz)
24
42
70
54
HPS Setting (psig)
Cutout
426 ± 7
Reset
320 ± 20
LPS Setting (psig)
Cutout
27 ± 4
Reset
67 ± 7
CONDENSATE DRAIN CONNECTION
Size (in.)...Type
3
/
4
...FPT
CONDENSER COIL
Copper Tubes — Aluminum Fins
Size (L x H) (in.)
40 x 15
40 x 16
40 x 22
Number of Rows...Fins/in.
4...13.6
4...17
4...13.6
CONDENSER FAN
Centrifugal — Direct Drive
Centrifugal — Belt Drive
Nominal Cfm
1350
1350
2250
2450
Maximum Rpm
1100
1500
Blower Size (in.)
12 x 6
12 x 9
Pulley Pitch Diameter (in.)
Blower
None
5.0
6.0
6.0
Motor (Variable)
None
2.4-3.4
1.9-2.9
2.4-3.4
Motor Hp
1
/
2
3
/
4
1
1
1
/
2
Motor Rpm
825
1725
1725
1725
EVAPORATOR COIL
Copper Tubes — Aluminum Fins
Size (L x H) (in.)
34 x 15
34 x 16
34 x 22
Number of Rows...Fins/in.
4...14.4
4...15
4...14.4
EVAPORATOR AIR FAN (Standard)
Centrifugal — Direct Drive
Nominal Cfm
800
1200
1600
2000
Max Rpm
1100
1150
900/1050**
Blower Size (in.)
10 x 5
10 x 6
10 x 6
Motor Hp (Rpm)
1
/
6
(850)
1
/
2
(1075)
3
/
4
(1050)
EVAPORATOR AIR FAN (Optional)
Not
Available
Centrifugal Belt Drive
Nominal Cfm
1600
2000
Max Rpm
1300
Blower Size (in.)
10 x 8
Motor Hp
1
1
/
2
Motor Rpm
1725
Pulley Pitch Diameter (in.)
Blower
4.2
Motor (Variable)
2.4-3.4
INDOOR-AIR FILTERS
Factory-Supplied Cleanable Type
Number...Size (in.)
1...14 x 34 x 1
1...21 x 34 x 1
INTERCONNECTING TUBING SIZE (in.)††
Hot Gas
1
/
2
1
/
2
1
/
2
1
/
2
Liquid
3
/
8
3
/
8
3
/
8
3
/
8
HPS
— High-Pressure Switch
LPS
— Low-Pressure Switch
Physical data
NOTE: Fasten threaded rods through holes in end frames. Use 2 rods
on each side of unit for a total of 4.
OPERATING WEIGHT DISTRIBUTION AND
CENTER OF GRAVITY
All panels must be in place when rigging.
UNIT
50AH
WEIGHT (lb/kg)
OF CORNER
DIMENSIONS
(ft-in./mm)
1
2
3
4
A
B
024
93/42 108/49 139/63 120/54 2-5
/737
2-1
5
/
8
/651
036
95/43 113/51 148/67 124/56 2-4
3
/
4
/730
2-2
/660
048
112/51 143/65 183/83 142/64 2-5
/737
2-3
/686
060
114/52 143/65 186/84 147/67 2-4
3
/
4
/730
2-2
3
/
4
/679