Carrier 50TCQ04---12 사용자 설명서

다운로드
페이지 44
44
CONFIGURATION POINTS (CON’T)
BACview
MENU
POINT NAME
BACnet
OBJECT
RANGE
DEFAULT
ENTRY
HOME
Select function below
CONFIG
CONFIGURATION
SERVICE
SERVICE CONFIGURATION
Unit Type
unit_type
1=Heat/Cool
2=HP O/B Ctrl
3=HP Y1/W1 Ctrl
Heat/Cool (TC and HC
models)
HP Y1/W1 Ctrl (TCQ
and HCQ models)
Compressor Stages
comp_stages
One stage/ Two
Stage
One Stage (sizes
04---07, and A08---A12)
Two Stages (sizes
08---30)
Economizer Exists
econ_exist
No/Yes
No (No FIOP)
Yes (FIOP)
Reversing Valve Type
rev_vlv_type
O output type/B
output type
O output type
Heat Type
heat_type
Electric/Gas
Gas (48 Series Units)
Electric (50 Series
Units)
Number of Heat Stages
heat_stages
1 / 2 / 0 (no heat)
0 (50 series cooling
only units)
1 (All TCQs and HCQs,
Low Nox units, single
phase gas units,
TC04---09 low and
TC05---07 med heat 3
phase gas units)
2 (TC04 and 08---09
med, TC05---09 high
heat 3 phase gas units,
HC04---09 3 phase gas
units and All 12---30
gas units)
Continuous Occupied Exhaust
occ_exh
No/Yes
No
Indoor CO2 Sensor Value @ Min mA
iaq_ref_lo_ppm
0---9999ppm
0
Indoor CO2 Sensor Value @ Max mA
iaq_ref_hi_ppm
0---9999ppm
2000
Outdoor CO2 Sensor Value @ Min
mA
oaq_ref_lo_ppm
0---9999ppm
0
Outdoor CO2 Sensor Value @ Max
mA
oaq_ref_hi_ppm
0---9999ppm
2000