 Test function and combustion analysis
The boiler has two pressure taps to measure the combustion gas 
temperature, the combustive air and the concentrations of O
2
 and CO
2
 
on the outside of the fl ue gas header.
To access these pressure taps, unscrew the screw which holds the 
blanking cover and its seal together.
Checking the gas setting
To carry out analyses of combustion, the test function must be 
activated.
Maximum gas fl ow combustion analysis
Activate the test function at the maximum heating power, pushing 
for 5 seconds the RESET until the yellow led blinks (also 60°C led is 
lit to indicate that Chimney is at max. CH absolute) The rotate the CH 
knob to the min., intermediate position or max position it’s possible 
to switch between min, max CH absolute and max DHW power 
(respectively the 40°C, 60°C and 80°C are lit to indicate the power 
level.
The function is automatically deactivated after 10 minutes or by 
pressing the RESET button.
Wait for the boiler to stabilise before carrying out the combustion 
analyses. Check the CO
2
 value according to the table below.
Important: do not remove silencer 17
N.B. When the front combustion chamber panel is open, the CO
2
 
value drops by 0.3%.
CO
2
 
maximum 
minimum
24
30
38
CO
2
 (%)
G20
9.0 ± 0.2
9.0 ± 0.2
9.4 ± 0.2
G31
10.7 ± 0.2
10.0 ± 0.2
10.6 ± 0.2
Minimum gas fl ow combustion analysis
Activate the test function at minimum power in either heating or 
domestic hot water production.
Wait for the boiler to stabilise before carrying out the combustion 
analyses. Check the CO
2
 value according to the table above.
Important: do not remove silencer 17
N.B. When the combustion chamber is open, the CO
2
 value drops 
by 0.3%.
If the values taken diff er from the table, adjust the gas valve following 
the procedure described below.
To adjust the CO
2
 value, remove cap, adjust the CO
2
 content to ± 0.2 by 
turning setting screw 51 (4 mm allen key)
 
- unscrew to lower the CO
2
 value
 
- tighten to increase the CO
2
 value
Set the content by turning the screw about a 1/4 of a turn then wait 
after each change for approximately 1 minute for the CO
2
 value to 
stabilise, then repeat.
Once the settings and analyses are complete, exit test mode by 
pressing Reset and reposition the blanking cover and its seal correctly.
Only a 2.5 key 
must be used
50
Only a 4 key must be used
Gas setting
24
30
38
G20
G31
G20
G31
G20
G31
lower Wobbe index  
15°C, 1013 mbar)  (MJ/m3)
45.67
70.69
45.67
70.69
45.67
70.69
gas valve restrictor(ø)
NO
3.80
NO
4.50
NO
5.25
gas fl ow max/min  
(15°C, 1013 mbar)
(nat - m3/h) (GPL - kg/h)
 max  D.H.W
2.65
1.94
3.17
2.33
4.02
2.95
 max  C.H.
2.33
1.71
2.96
2.17
3.28
2.41
 min
0.58
0.43
0.69
0.50
0.79
0.58
If the values taken diff er from the table, adjust 
the gas valve following the procedure described 
below.
Adjust the CO
2
 content to ± 0.2 by turning 
setting screw 50 (2.5 mm allen key)
 
- tighten to lower the CO
2
 value
 
- unscrew to increase the CO
2
 value
Set the content by turning the screw about a 
1/4 of a turn then wait after each change for 
approximately 1 minute for the CO
2
 value to 
stabilise, then repeat.