User’s Information Manual
2  
Maintenance schedule
5
Service technician
(see the Knight Wall Mount Service Manual)
General: 
 
• Reported problems
 
• Inspect interior; clean and vacuum if 
  
necessary
 
• Clean condensate trap and fill with fresh 
  
water
 
 Check for leaks (water, gas, flue, 
  
condensate)
 
• Verify flue and air lines in good condition 
 
  and sealed tight
 
• Check system water pressure/system 
  
piping/expansion 
tank
 
• Check control settings
 
• Ignition and flame sense electrodes 
   (sand off any deposits; clean and 
  
reposition)
 
• Wiring and connections
  • Perform start-up checkout and 
      performance verification per Section 10 
        in the Knight Wall Mount Installation and 
       Operation Manual.
 
• Flame inspection (stable, uniform)
 
• Flame signal (at least 4 mA)
 
 Clean the heat exchanger if flue 
 
 temperature is more than 54°F above 
 
  return water temperature.
If combustion or performance 
indicate need:
 
 • Clean heat exchanger
 
 
 •
 Remove and clean burner using 
 
   compressed air only 
 
 • Clean the blower wheel 
Owner maintenance
(see pages 6 - 8 for detailed instructions)
Daily
 
• Check boiler area
 
     Check pressure/temperature 
  
 
gauge
Monthly
 
• Check vent piping
 
• Check air piping
 
• Check air and vent termination 
  
screens
 
• Check relief valve
 
• Check condensate drain system
 
Periodically
 
• Test low water cutoff (if used)
 
• Reset button (low water cutoff)
Every
6 months
 
• Check boiler piping (gas and 
 
  water) for leaks
 
• Operate relief valve
End
of season 
months
 
•  Shut boiler down (unless boiler 
 
   used for domestic hot water)
 WARNING
Follow the maintenance procedures given throughout this manual.  Failure to perform the service and 
maintenance or follow the directions in this manual could result in damage to the boiler or system, 
resulting in severe personal injury, death, or substantial property damage.
ANNUAL START-UP