Lochinvar 1.0- 1.3- 1.5 사용자 설명서

다운로드
페이지 24
8
Modbus Instructions
Input Registers
Address
Description
Default
Unit
Min.
Max.
Resolution
30001
Discrete Inputs 1 - 16
0
NA
0
65535
1
30002
Discrete Inputs 17 - 32
0
NA
0
65535
1
30003
Discrete Inputs 33 - 48
0
NA
0
65535
1
30004
System / Cascade Setpoint
0
Degrees Celsius
0
130
0,5
30006
Cascade Total Power
0
%
100
800
1
30007
Cascade Current Power
0
%
0
800
1
30008
Outlet Setpoint 1
0
Degrees Celsius
0
130
0,5
30009
Outlet Temperature 1
0
Degrees Celsius
0
130
0,1
30010
Inlet Temperature 1
0
Degrees Celsius
-20
130
0,1
30011
Flue Temperature 1
0
Degrees Celsius
-20
130
0,1
30012
Firing Rate 1
0
%
0
100
1
30014
Boiler 1 Status Code
0
NA
0
65535
1
30015
Boiler 1 Blocking Code
0
NA
0
65535
1
30016
Boiler 1 Lockout Code
0
NA
0
65535
1
30017
Outlet Setpoint 2
0
Degrees Celsius
0
130
0,5
30018
Outlet Temperature 2
0
Degrees Celsius
0
130
0,1
30019
Inlet Temperature 2
0
Degrees Celsius
-20
130
0,1
30020
Flue Temperature 2
0
Degrees Celsius
-20
130
0,1
30021
Firing Rate 2
0
%
0
100
1
30023
Boiler 2 Status Code
0
NA
0
65535
1
30024
Boiler 2 Blocking Code
0
NA
0
65535
1
30025
Boiler 2 Lockout Code
0
NA
0
65535
1
Holding Registers
40001
Configuration
0
NA
0
65535
1
40002
Coils
0
NA
0
65535
1
40003
0-10 Volt Input / Rate Command /
Setpoint Command
0
%
0
100
1
40004
Tank Setpoint
0
Degrees Celsius
0
87,5
0,5
40005
Tank Temperature
0
Degrees Celsius
-20
130
0,1
40006
Outdoor Temperature
0
Degrees Celsius
-40
60
0,1
40007
System Supply Temperature
0
Degrees Celsius
-20
130
0,1
SYNC Boiler Memory Map
3  
Memory Map 
Configuration Bits
Address 40001 contains configuration bits sent from the BAS to the boiler.  These bits tell the boiler to use its own internal inputs,
or inputs from the BAS.  When a bit is set to 1, the boiler will ignore the corresponding value contained internally, and expect the
BAS to write that value into the Holding Registers.  The configuration bits are as follows:
Bit 4:  System Supply Temperature
Bit 5:  Outdoor Temperature
Bit 6:  Tank Temperature
Bit 7:  System Return Temperature
Bit 8 - 15:  Not Used (Default = 0)
Bit 0 (LSB):  Boiler Enable
Bit 1:  Tank Thermostat
Bit 2:  Rate Command / 10 - 10V Input / Setpoint Command
Bit 3:  Tank Setpoint