Maintenance
Maintenance and annual startup
Table 9A Service and Maintenance Schedules
Service technician
(see the following pages for instructions)
General:
 
• Address reported problems
 
• Inspect interior; clean and vacuum if 
  
necessary; 
 
• Clean condensate trap and fill with fresh 
  
water
 
 Check for leaks (water, gas, flue, 
  
condensate)
 
• Verify flue and air openings in good 
        condition and free of obstruction
 
• Check system water pressure/system 
  
piping/expansion 
tank
 
• Check control settings
 
• 
 
Check ignition and flame sense 
       electrodes (sand off any deposits; clean 
  
and 
reposition)
 
• Check wiring and connections
 
 Perform start-up checkout and 
 
 performance verification per Section 7 
 
  of this manual.
 
• Flame inspection (stable, uniform)
 
• Flame signal (at least 10 microamps at 
 
   high fire)
 
 Clean the heat exchanger if flue 
 
 temperature is more than 54°F above 
 
  return water temperature.
If combustion or performance 
indicate need:
 
 • Clean heat exchanger
 
 
 •
 Remove and clean burner using 
 
   compressed air only 
 
 • Clean the blower wheel 
ANNUAL START-UP
Owner maintenance
(see the Outdoor Knight User’s Information Manual 
for instructions)
Daily
 
• Check boiler area
 
  Check pressure / temperature  
        gauge
Monthly
 
• Check air and vent termination 
 
   screens
 
 
• Check relief valve
 
• Check condensate drain system
 
Periodically
 
• Test low water cutoff (if used)
 
• Reset button (low water cutoff)
Every
6 months
 
• Check boiler piping (gas and 
 
  water) for leaks
 
• Operate relief valve
End
of season 
months
 
 
 
•  Shut boiler down (unless boiler 
 
  used for domestic hot water)
49
     
Outdoor Knight Boiler Installation & Operation Manual