Lennox International Inc. GSB8-S 사용자 설명서

다운로드
페이지 36
28
MAINTAINING YOUR BOILER
Keep boiler area clear and free from combustible materials, 
gasoline and other fl ammable vapors and liquids. Keep 
boiler are clear and free of obstructions to fl ow of 
combustion and ventilation air.
Check the water level every day or two. Verify the water 
line shown by operating the drain valve on the gauge. BE 
SURE TOP AND BOTTOM VALVES ON GAUGE ARE ALWAYS 
OPEN SO THAT ACTUAL WATER LEVEL WILL BE SHOWN AT 
ALL TIMES.
The gauge glass should be dry above the water line. The 
water line should not bounce more than about one inch 
when the boiler is steaming. If you see water droplets 
carrying over through the top of the gauge glass, or 
excessive bouncing of the water line, the boiler needs to 
be cleaned. Follow the instructions under “Cleaning Your 
Boiler.”
SAFETY VALVE
Before testing, make certain discharge pipe is properly 
connected to valve outlet and arranged to contain and 
safely dispose of boiler discharge. Under normal operating 
conditions a “try lever test” must be performed every 
month. A “try lever test” must also be performed at the 
end of any non-service period. Test at normal system 
operating pressure by holding the test lever fully open 
for at least fi ve seconds to fl ush the valve seat free of 
sediment and debris. Then release lever and permit the 
valve to snap shut. If lift lever does not activate, or there 
is no evidence of discharge, turn off boiler immediately and 
contact a licensed contractor or qualifi ed service personnel.
LOW WATER CUT-OFF
The Low Water Cut-Off will interrupt the electrical current 
to the burner when the water line in the boiler drops to a 
low level.
On fl oat type low water cutoffs, it is very important to 
keep the fl oat chamber free from sediment, a condition 
essential to dependability. To keep any accumulation from 
interfering with fl oat action is to “BLOW DOWN” or fl ush out 
the control regularly. This must be done two to three times 
during the fi rst week after installation and once a week 
thereafter during the heating season. Do it while the boiler 
is in operation. First note water level in gauge glass. Open 
blow-off valve at bottom of control; water will pour out, 
fl ushing away sediment. Drain until water is clear, about a 
pailful, then close valve. If water level in gauge glass has 
dropped, add water to boiler to restore level. Consult low 
water cut-off manufacturer’s instructions included with 
boiler.
NOTE: Opening blow-off valve checks cut-off operation 
too. As fl oat drops with falling water level, burners will shut 
off. After valve is closed and normal operating conditions 
are restored, burners will resume fi ring. For probe type 
Low Water Cutoffs, check action of the Low Water Cut-Off 
monthly to make sure it is providing the proper protection. 
See “Checking and Adjusting” on page 19. Low Water Cut-
Off remote probes must be removed for periodic inspection 
and cleaning, preferably at the beginning of each heating 
season. More frequent cleaning may be required on boilers 
requiring constant or very frequent additions of make up 
water.
BURNERS
A visual check of the pilot and main burner fl ames should 
be made at least once each year, preferably at the begin-
ning of the heating season. See page 19.
BOILER FLUE PASSAGES
Under normal operating conditions, with the burners 
properly adjusted, it should not be necessary to clean the 
boiler fl ue gas passages. However, to assure trouble-free 
operation, we recommend that you have the fl ue passages, 
burner adjustment, 
and operation of the controls checked once each year by a 
competent Service Technician.
Before the start of each season (or whenever system has 
been shut down for some time) recheck the whole sys-
tem for leaks . . . and recheck the boiler and vent pipe for 
leaks.
VENT PIPE
The venting of this unit is very important and the piping 
should be checked at least once a season. If the vent pip-
ing shows any sign of leaking, replace it immediately.
CLEANING YOUR BOILER FLUE PASSAGES AND 
BURNERS
Flue Passages between sections should be examined yearly 
and cleaned, if necessary. To clean, remove burners, pilot, 
and vent pipe. Remove top and front jacket panels. Remove 
the two screws attaching the intermediate front panel to 
the left and right side jacket panels. Remove the draft 
diverter and intermediate front panel as a unit. Carefully 
remove the cerafelt gasket strips. Clean passageways 
between sections with a fl exible handle wire brush. Remove 
dirt from bottom of boiler and from between sections by 
vacuuming. Make sure all fl ame ports in burners are open 
and clear. Shake out or blow out all loose dirt in burners. 
Reseal seams between adjacent sections as necessary with 
400F RTV silicone sealant. Reassemble all parts. Be sure to 
check tightness of pilot connections and condition of burner 
fl ames after reassembly (see Figures 18 and 19). 
Be sure vent pipe connections to chimney are secure and 
no obstructions are present.