Lochinvar 2.5 사용자 설명서

다운로드
페이지 60
1  
Determine boiler location
        
Installation & Operation Manual
Combustion and ventilation air 
requirements for appliances drawing air 
from the equipment room
Provisions for combustion and ventilation air must be in 
accordance with Air for Combustion and Ventilation, of the 
latest edition of the National Fuel Gas Code, NFPA 54 / ANSI 
Z223.1, in Canada, the latest edition of CGA Standard B149 
Installation Code for Gas Burning Appliances and Equipment, 
or applicable provisions of the local building codes.
The equipment room MUST be provided with properly sized 
openings and/or be of sufficient volume to assure adequate 
combustion air and proper ventilation for all gas fired appliances 
in the equipment room to assure adequate combustion air and 
proper ventilation.
The requirements shown are for the appliance only; additional 
gas fired appliances in the equipment room will require an 
increase in the net free area and/or volume to supply adequate 
combustion air for all appliances.
No combustion air openings are needed when the appliance is 
installed in a space with a volume NO LESS than 50 cubic feet 
per 1,000 Btu/hr of all installed gas fired appliances and the 
building MUST NOT be of “Tight Construction”
3
.
A combination of indoor and outdoor combustion air may 
be utilized by applying a ratio of available volume to required 
volume times the required outdoor air opening(s) size(s).  This 
must be done in accordance with the National Fuel Gas Code, 
NFPA 54 / ANSI Z223.1.
Figure 1-5_Combustion Air Through Ducts
2.  If combustion and ventilation air is taken from the 
 
outdoors using a duct to deliver the air to the 
 
equipment room, each of the two openings should be 
 
sized based on a minimum free area of one square inch 
 
per 2000 Btu/hr (11 cm
2
 per kW) of input (see FIG. 1-5).
Figure 1-6_Combustion Air from Interior Space
3.  If air is taken from another interior space combined with 
 
the equipment room:
(a)  Two spaces on same story:  Each of the two openings 
 
specified above should have a net free area of one square 
 
inch for each 1000 Btu/hr (22 cm
2
 per kW) of input, but 
 
not less than 100 square inches (645 cm
2
) (see FIG. 1-6).
(b)  Two spaces on different stories:  One or more openings 
 
should have a net free area of two square inches per 1000 
 
Btu/hr (44 cm
2
 per kW).
Figure 1-4_Combustion Air Direct from Outside
1.  If air is taken directly from outside the building 
 
with no duct, provide two permanent openings to 
 
the equipment room each with a net free area of one square 
 
inch per 4000 Btu/hr input (5.5 cm
2
 per kW) (see FIG. 1-4).
Figure 1-7_Combustion Air from Outside - Single Opening
12