Table 6B Natural Gas Pipe Size Chart
The gas piping must be sized for the proper flow and length of 
pipe, to avoid excessive pressure drop.  Both the gas meter and 
the gas regulator must be properly sized for the total gas load.  
If you experience a pressure drop greater than 1 inch w.c. 
 
 
 
 
 
 
(249 Pa), the meter, regulator, or gas line is undersized or in 
need of service.  Perform the steps below when checking inlet 
gas supply:
1.  Turn the main power switch to the “OFF” position.
2.  Shut off gas supply at the manual gas valve in the gas 
 
piping to the appliance.  
3.  Remove the 1/8" pipe plug on the flange to the factory 
 
supplied gas shutoff valve and install a suitable 1/8" 
 
fitting (field supplied) for the manometer tubing.  Place the 
 
tubing of the manometer over the tap once the 1/8" 
 
fitting is installed as shown in FIG. 6-4.
4.  Slowly turn on the gas supply at the factory installed 
 
manual gas valve.
5.  Turn the power switch to the “ON” position.
6.  Adjust the temperature set point on the control panel of 
 
the SMART TOUCH control module to call for heat or 
 
utilize Service Mode, see page 44 of this manual.
7.  Observe the gas supply pressure as the burner fires at 
 
100% of rated input.  Percent of burner input will be 
 
displayed on the Modulation Screen.
8.  Ensure inlet pressure is within specified range. 
 
 
Minimum and maximum gas supply pressures are 
 
specified in this section of the manual.
9.  If gas supply pressure is within normal range and no 
 
adjustments are needed, proceed on to Step 11.  
10.  If the gas pressure is out of range, contact the gas utility, 
 
gas supplier, qualified installer or service agency to 
 
determine the necessary steps to provide proper gas 
 
pressure to the control.
11.  Turn the power switch to the “OFF” position.
12.  Shut off the gas supply at the manual gas valve in the gas 
 
piping to the appliance.  
13.  Remove the manometer from the pressure tap on top of 
 
the gas valve.  Remove the 1/8" (3 mm) field supplied 
 
fitting and reinstall the pipe plug removed in Step 3.
DO NOT adjust or attempt to measure gas 
valve outlet pressure.   Attempting to alter 
or measure the gas valve outlet pressure 
could result in damage to the valve, causing 
potential severe personal injury, death, or 
substantial property damage.
 WARNING
TABLE - 6B
GAS PIPING SIZE CHART
Nominal
Iron Pipe
Size
Inches
Length of Pipe in Straight Feet
Maximum 
Capacity of Pipe 
in Thousands 
of Btu/hr for 
gas  pressures  of      
14 Inches Water 
Column (0.5 
PSIG) or less and 
a pressure drop 
of 0.5 Inch Water 
Column (Based 
on NAT GAS, 
1025 Btu/hr per 
Cubic Foot of 
Gas and 0.60 
Specific Gravity)
10
20
30
40
50
60
70
80
90
100
125
150
175
200
2,150
1,500
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
2
4,100
2,820
2,260
1,950
1,720
1,560
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
6,460
4,460
3,610
3,100
2,720
2,460 2,310 2,100
2,000
1,900
1,700 1,540
N/A
N/A
3
11,200
7,900
6,400
5,400
4,870
4,410 4,000 3,800
3,540
3,300
3,000 2,720 2,500
2,340
4
23,500 16,100 13,100 11,100 10,000 9,000 8,300 7,690
7,380
6,870
6,150 5,640 5,130
4,720
Check inlet gas supply
6  
Gas connections 
(continued)
  
        
Installation & Operation Manual