Can
adian Comfort Industries      V05                                            
18                                         
 VULCAN “V” SERIES OWNERS MANUAL 
Copyright 2005                                                                     
                                                
Dansons Group Inc.
 
M
OBILE 
H
OME 
I
NSTALLATION
 
 
CAUTION:   DO NOT INSTALL STOVE IN SLEEPING ROOM 
 
THE STRUCTURAL INTEGRITY OF THE MANUFACTURED HOME FLOOR, 
CEILING/ROOF MUST BE MAINTAINED! 
 
Your VULCAN “V” SERIES stove has been tested and listed for mobile home installation. It may be installed 
in a mobile home as a "Free Standing Stove", a "Hearth Stove", as an "Insert" installed in an existing wood or 
coal-burning fireplace or as an "Built –In Insert" installed with a mantel.  
 
In addition to all previously detailed installation requirements, mobile home installations 
must meet the following requirements: 
 
Permanently bolt your stove to the floor, (A). Figure 23, 24  
 
Electrically ground your stove or the pedestal to the steel frame of the home. Use a number 8 gauge copper 
wire, (B) figure 24, or equivalent. 
 
The stove must have a permanent outside air source with a ¼ inch screen over the inlet. 
Figure 23, (B,C, D) 
  
For transportation all chimney / vent above the mobile home must be removed. 
 
“PL” or ”L” Vent must be 3” or 4”  and must extend a minimum or 36” above the roofline of the mobile 
home and must be installed using a UL/ULC listed ceiling fire stop (J), figure 23,  and  
rain cap (L), figure 23.  
INSTALL VENT AT CLEARANCES SPECIFIED BY THE VENT MANUFACTURER. 
Floor Pad 
Combustion Air Intake 
Fresh Air Duct 
Fresh Air Hood 
Stove Exhaust 
Pipe Adapter 
Clean Out Tee 
Tee Support Bracket 
Pipe 
Firestop Spacer / Ceiling Support 
Roof Flashing / Storm Collar 
Rain Cap  
 
 
 
 
 
 
 
 
 
 
 
 
 
                                            Figure 23 
 
 
 
 
 
 
         Figure 24 
Note
: When moving your Mobile Home, all exterior venting must be removed while Mobile Home is 
being relocated. Upon completion of relocation all venting must be reinstalled and securely fastened. 
B
A
C D
G
H
I
J
K
L
FRAME
HEARTH PAD
FLOOR
B
GROUND
WIRE
A
BOLT(S)