FLUE SYSTEM 
 
Caution: Follow the pipe manufacturer’s installation instructions and directions for passing 
through combustible walls and ceilings.   
Be sure to check local codes in your area. 
 
NOTE:  See the installation drawing later in this manual (Illustration 1). 
This unit is equipped with a negative draft system that pulls combustion air through the 
burn pot and pushes the exhaust air out of the dwelling. If this unit is connected to the flue 
system other than the way explained in this manual, it will not function properly.  
For any of 
these installations, keep in mind that each elbow used reduces draft by up to 30%; it is good practice 
to add 3’ (three feet) of vertical rise for each elbow used.  Example:  After the 2
nd
 elbow used, add 6’ 
(six feet) of vertical rise before terminating your vent pipe. 
 
Corn Vent Pipe 
The UL approved corn vent pipe that we recommend is a twist lock system; however, it is still 
recommended that high temperature silicone be used at each joint.  England’s Stove Works 
recommends the use of Simpson Dura-Vent
® twist-lock pipe  (if you use other pipe, consult your 
local building codes and/or building inspectors, and secure each joint with at least three screws—see 
Important Information, above).  Do not use “B” vent gas pipe or galvanized pipe with this unit. The 
corn pipe is designed to disassemble for cleaning and should be checked several times during the 
burning season — corn vent pipe is not furnished with the unit and must be purchased separately.  
Do not install a flue damper of any kind in this system, and do not connect this unit to a flue 
system serving another heating appliance.   
 
Through the Wall 
To vent the unit through the wall, connect the pipe adapter to the exhaust motor adapter. If the 
exhaust adapter is at least eighteen inches (18”) above ground level, a straight section of corn pipe 
can be used to initially pass through the wall (see Illustration 1). Your dealer or our factory should 
be able to provide you with a kit that will handle most of this installation, which will include a wall 
thimble that will allow the proper clearances through a combustible wall. Once outside the structure, 
a three-inch (3”) clearance should be maintained to the outside wall and a clean out tee should be 
placed on the pipe that extends through the wall. We recommend a minimum of three feet (3’) of 
vertical pipe with a 90-degree turn away from the house. At this point, a one-foot (1’) section and 
horizontal cap will complete the installation (see Illustration 1).  
 
A wall strap should be placed just below the last 90-degree section to make the system more 
stable. If you live in an area that has heavy snowfall, it is recommended the installation be taller than 
three feet (3’) to get above the snowdrift line.   
 
The same type installation can be used if your stove is below ground level by adding the clean-
out section and vertical pipe inside until ground level is reached.  However, we recommend 
basement installation be performed only by a professional installer.  For basement installations, a 3” 
(three inch) pipe and coupler must be used for Outside Combustion Air, and a minimum clearance of 
3’ (three feet) must be maintained outside the dwelling from the ground to the Corn Vent Exhaust 
Pipe.  
 
The through-the-wall installation is the least expensive and simplest installation.  In a through-
the-wall installation you should be mindful of the snowdrift line, as well as dead grass and leaves.  
We recommend a three foot (3’) minimum vertical rise on the inside or the outside of the dwelling.  
Never terminate the end vent under a deck, in an alcove, under a window or between two windows.   
 
Call (800) 516-3636 to inquire about the AC-33000 Through-the-Wall Kit or  
 