hot enough to cause burns if touched by children. Non-combustible shielding or guards may be required.
3.  Termination must exhaust above the inlet elevation. It is recommended that at least five feet of vertical pipe be 
installed outside when the appliance is vented directly through a wall, to create some natural draft to prevent the 
possibility of smoke or odor during appliance shut down or power failure. This will keep exhaust from causing a 
nuisance or hazard from exposing people or shrubs to high temperatures. In any case, the safest and preferred 
venting method is to extend the vent through the roof vertically.
4.  Distance from the bottom of the termination and grade is 12” (30 cm) minimum. This is conditional upon the 
plants and nature of grade surface. The exhaust gases are hot enough to ignite grass, plants and shrubs located 
in the vicinity of termination. The grade surface must not be lawn.
5.  If the unit is incorrectly vented or the air to fuel mixture is out of balance, a slight discoloration of the exterior 
of the house might occur. Since these factors are beyond the control of Sherwood Industries Ltd, we grant no 
guarantee against such incidents.
NOTE: Venting terminals shall not be recessed into walls or siding.
Installation
V
ENT
 T
ERMINATION
 R
EQUIREMENTS
:
IT IS RECOMMENDED THAT YOUR PELLET STOVE BE INSTALLED BY AN AUTHORIZED DEALER/INSTALLER. 
Figure 16: Use in conjunction with Table 1 for allowable exterior vent termination 
locations. 
Table 1: Use in conjunction with Figure 16 for allowable exterior vent termination locations. 
Letter
Minimum Clearance
Description
A
24 in (61 cm)
Above grass, top of plants, wood, or any other combustible materials.
B
48 in  (122 cm) 
Beside/below any door or window that may be opened. (18” (46 cm) if outside 
fresh air install.) 
C
12 in (30 cm)
Above any door or window that may be opened. (9” (23 cm) if outside fresh air 
install.) 
D
24 in (61 cm)
To any adjacent building, fences and protruding parts of the structure.
E
24 in (61 cm)
Below any eave or roof overhang
F
12 in (30 cm)
To outside corner.
G
12 in (30 cm)
To inside corner, combustible wall (vertical and horizontal terminations).
H
3 ft (91 cm) within a height 
of 15 ft (4.5 m) above the 
meter/regulator assembly
To each side of center line extended above natural gas or propane meter/
regulator assembly or mechanical vent.
I
3 ft (91 cm)
From any forced air intake of other appliance
J
12 in (30 cm)
Clearance to non-mechanical air supply inlet to building, or the combustion air 
inlet to any appliance.
K
24 in (61 cm)
Clearance above roof line for vertical terminations.
L
7 ft (2.13 m)
Clearance above paved sidewalk or paved driveway located on public property.
Air Supply Inlet
Gas Meter
Restriction Zone
(Termination not allowed)
Termination Cap
G
G
Opens
Opens
Opens
D
F
B
B
A
I
H
K
G
G
L
C
E
1. Do  not  terminate  the 
vent  in  any  enclosed  or 
semi-enclosed  areas  such 
as  a  carport,  garage, 
attic,  crawlspace,  narrow 
walkway,  closely  fenced 
area,  under  a  sundeck 
or  porch,  or  any  location 
that  can  build  up  a 
concentration  of  fumes 
such as stairwells, covered 
breezeway, etc.