NFPA Standard-Specific Requirements
MS-9200UDLS PN 52750:A 11/04/05
175
NFPA 72 Auxiliary Fire Alarm System
All connections are power-limited and supervised. This application is not suitable for
separate transmission of sprinkler supervisory or trouble conditions.
separate transmission of sprinkler supervisory or trouble conditions.
Notes:
1. 3 ohms maximum loop resistance allowed for wiring from control panel to
Municipal Box.
2. Cut JP3 on the MS-9200UDLS main circuit board to supervise placement of
4XTMF module and circuit.
3. Cut JP2 on the MS-9200UDLS main circuit board to enable FACP Supervisory
relay.
4. Refer to "4XTMF Transmitter Module Installation" on page 38 for detailed
information.
Figure C.1 Municipal Box Connected to F Transmitter Module
FIRE
Gamewell Model M34-56
Local Energy Municipal Box
Local Energy Municipal Box
Polarities shown in alarm condition
+
Nonpower-limited
Municipal Box
Circuit
Circuit
+
-
-
F
Figure C.1 Municipal Box Connected to 4XTMF Transmitter Module