3.6.8  Walktest
Walktest allows an individual to test the fire alarm system without the necessity to reset 
the control panel after each device activation.  Pressing 2 while viewing the Programming 
Screen #3 will cause the following Walktest options to be displayed:
To perform a silent walktest which will not sound the NACs, press 1 while viewing the 
Walktest Screen.  To perform an audible walktest, which will sound the NACs, press 2 
while viewing the Walktest Screen.  When either option is chosen, the panel will enter 
Walktest Mode and the following screen will be displayed:
The user can now perform a one-person walktest by activating devices throughout the 
system.  As each device is activated, the screen will display the information about the 
activated device as shown below.  Note that the colon in the time is replaced with an 
asterisk to distinguish the walktest screen from an actual alarm screen.  
After completion of the Walktest, press the Esc (Escape) key to exit Walktest Mode and 
return to the Walktest Screen.  The results of the Walktest can now be viewed by pressing 
3 while viewing the Walktest Screen.  The following screen will be displayed:
Use the up and down arrow keys to view all of the walktest results which will be displayed 
as illustrated in the preceding screen.  Note that the Walktest log is stored in RAM.  If all 
power (AC and DC) is removed from the FACP, the Walktest log information will be lost.  
This information is also overwritten when subsequent walktests are performed.
    PROGRAMMING
1=HISTORY
2=WALKTEST
3=OPTION MODULES
Programming Screen #3
@@@@@WALKTEST
1=SILENT
2=AUDIBLE
3=VIEW@RESULT
Walktest Screen  
     
@UNIT@IN@WALKTEST
Walktest Active Screen  
ALARM@@PULL@STATION
@@@@@<ADJ>@<NOUN>
@@@@@@@@@@@@@@@Z000
@10*00A@010801@1M001
@@WALKTEST@RESULTS
View Result Screen