History
i
Notice!
If a system without a D7039 Multiplex Expansion Module loses all power (AC and standby bat-
tery), all history events are cleared.
 
The HISTORY option is a chronological list of system events that occurred. Press the [History]
key to HISTORY select from the Main Menu (SYSTEM NORMAL display).
On an FPD-7024 FACP with a D7039 Multiplex Expansion Module, up to 499 History events are
supported.
On an FPD-7024 FACP without a D7039 Multiplex Expansion Module, up to 99 History events
are supported.
After you press the [History] key, the most recent system event appears on the top line of the
LCD with the time and date below it.
Example: (Assume you pressed the [History] key at the Main Menu):
While the first event shows, the bottom line toggles every four seconds between the time and
date that the event occurred.
To return to a previous screen in the history buffer, press [2/▲].To scroll to the next event
record, press [8/▼].
For abbreviations used in history events, see the following table:
Abbreviation
Meaning
 
Abbreviation
Meaning
ALRM
Alarm
 
OFFNORM
Off Normal at Test
ARST
Alarm Restore
PH1
Phone Line 1
AUTOTST
Auto Test
PH2
Phone Line 2
BATT:LOW
Battery Low
RSTR
Restore
BAT:RSTR
Battery Restore
S
Supervisory
CPUFLT
Internal Error
SMK:FLT
Smoke Power Fault
DBL
Disable
SYSRESET
System Reset
DRILL:BEG
Drill Begin
SYSRST
System Restore
DRILL:OVR
Drill Over
SYSTRB
System Trouble
DRST
Dirty Restore
SYS:WDOG
Automatic CPU Reset
(Watchdog)
DRTY
Dirty
TRBL
Trouble
DSBL
Disable
TRST
Trouble Restore
EE2
EEPROM
TST:BEG
Test Begin
ENBL
Enable
TST:OVR
Test Over
F
Fire
W
Waterflow
MANULTST
Manual Test
 
Table 6.2: History event abbreviations
 