Honeywell 5820XL 사용자 설명서

다운로드
페이지 228
Before You Begin Installing
151209
3-7
3.6.2
Current Draw Worksheet for SK SLC Devices
Use Table 3-1 to determine current requirements during alarm/battery standby operation when 
SK SLC devices are installed. You can install up 99 SK detectors per loop (396 max per 
panel) and 99 SK modules per loop (396 max per panel). Copy this section if additional space 
is required.
Table 3-1: Current Draw Worksheet for SK SLC Devices
Device
# of Devices
Current per Device
Standby 
Current
Alarm 
Current
For each device use this formula:      This column      X      This column               =      Current per number of devices.
Fire Panel (Current draw from 
battery)
1
Standby:
215 mA
215 mA
Alarm:
385 mA
385 mA
Addressable SLC Detectors
SK-Photo
(99 max/loop 
& 396 max/
panel)
1
Standby/Alarm:
0.27 mA
mA
mA
SK-Photo-T
mA
mA
SK-Ion
mA
mA
SK-Heat
mA
mA
SK-Heat-HT
mA
mA
SK-Beam (without integral test)
SLC
Standby/
Alarm:
 2 mA
Aux. Pwr
Standby:
 2 mA
mA
Alarm:
 8.5 mA
mA
SK-Beam-T 
5
(with integral test)
SLC
Standby/
Alarm:
 2 mA
Aux. Pwr
Standby:
 2 mA
mA
Alarm:
 8.5 mA
mA
SK-Duct
6
SLC
Standby/
Alarm:
 0.27 mA
mA
mA
SK-Acclimate
Standby/Alarm:
0.3 mA
mA
mA
SK-Heat-ROR
mA
mA