CANON    Digital Galvano Scanner System
 
KP-1SM Series + GC-251 
Users Manual 1.00 
 
 
 
  
19
For the ROM Write of the parameter, a reply with data has been sent by all means by a controller. 
The content of data is different by a parameter.    (For details, see 7-3, “Parameter Details.”) 
Note)  Please make the ROM write of the parameter after enough confirmation.    Depending on 
value for change, the controller may not start normally.
 
 
    Parameter ROM Write send 
     
E        Axis
 No.        P        Command ID        /        Data          Delimiter 
 
 
 
 
 
 
 
         
E.g.  LQ gain parameter  ID = 6    Data = 4500 
           E1P006 / 4500 (LF) 
                            (ASCII code: 0x45 0x31 0x50 0x30 0x30 0x36 0x2f 0x34 0x35 0x30 0x30 0x0a) 
                                                      E        1        P      0        0        6        /      4          5        0      0      (LF) 
 
 
   Parameter ROM Write reply 
     
E        Axis
 No.        P        Command ID        /        Data          Delimiter 
 
 
 
 
 
 
 
         
E.g.  LQ gain parameter  ID = 6    Data = 4500 
           E1P006 / 4500 (LF) 
                            (ASCII code: 0x45 0x31 0x50 0x30 0x30 0x36 0x2f 0x30 0x0a) 
                                                      E        1        P      0        0        6        /        0      (LF) 
 
 
 
Axis No. 
1 or 2 
Command ID 
Decimal, 3-digit 
(See 7-1 for details)
Parameter setting 
Decimal 
Parameter 
Delimiter
LF or CR 
Axis No. 
1 or 2 
Command ID 
Decimal, 3-digit 
(See 7-1 for details)
Parameter setting 
successful / unsuccessful 
0 or 1 
Parameter 
Delimiter
LF or CR