119076.02 TELEPRESENCE T3 ROOM REQUIREMENTS 12.08
TANDBERG
Telepresence T3
HVAC REQUIREMENTS
The following HVAC (heating, ventilation, air-conditioning) requirements apply to 
the TANDBERG Telepresence T3:
Power consumption System:  1725 W
Power consumption Table: 
300 W
Power consumption Lighting:  1300 W
 Noise from air-conditioning should be less or equal to 27 dB(A) measured at 
all seating positions.
Make sure that HVAC mounting neither conflicts with the ceiling lights positions 
nor the document camera position.
A detailed drawing of the ceiling mounting of the lights can be found overleaf, 
while the drawing 119082 on page 14 shows the position of the document camera.
Note:
 Dimensions are between floor and 
underside of light modules.
Note:
 The HVAC equipment must 
not 
be mounted in a way so that it prevents 
correct mounting of the ceiling lights and the 
document camera. Consult the TANDBERG 
Telepresence T3 Room Installation Guide for 
more on this.
228 cm 
7’5
3
4
Ce
nte
rlin
e
Tip!
 An average person emits approximately 
65 W at rest. You may want to consider this 
when calculating the HVAC requirements.