2.1.4
Visibility of tags
For personal and system safety, all tags attached to the transmitter housing must remain visible. Clean 
or replace them as necessary.
2.2
Transmitters approved for ATEX Zone 1
If the transmitter carries an ATEX Zone 1 approval, wiring compartments are labeled as shown in 
Figure 2-2.
The sensor wiring compartment is rated EEx i (intrinsically safe), and may be opened at any 
time. See Label 1 in Figure 2-2.
The field wiring compartment is rated EEx e (increased safety), and should remain closed 
when power is on. See Label 2 in Figure 2-2.
The circuit board compartment is rated EEx d (flameproof), and should remain closed at all 
times after the transmitter has been installed. If the transmitter is approved by ATEX as 
flameproof, the compartment has a lockout device, shown in Figure 2-2. The lockout device 
must be loosened and rotated before the compartment cover can be unscrewed.
WARNING
Explosion hazard
The circuit board compartment is rated EEx d 
(flameproof), and should remain closed at all times after 
the flowmeter has been installed.
To avoid risk of explosion in an explosive atmosphere:
Read label that points to compartment cover before 
accessing circuit board compartment. Figure 2-2 
shows the location of the labels on the transmitter 
housing.
Shut off power, and wait at least 2 minutes before 
removing EEx d (circuit board) compartment cover. 
Figure 2-2 also identifies the EEx e (field wiring), EEx i 
(sensor wiring), and EEx d (circuit board) 
compartments.