Model IFT9701 Transmitter Instruction Manual
39
Configuration with a HART Communicator
 continued
Co
nfig
uratio
n wit
Co
mm
u
n
ic
ato
r
T
ro
u
b
lesho
ot
ing
Con
fig
ur
atio
n
 w
ith
 Pr
oL
in
II
Flo
w
meter Star
tup
To enter an internal damping value, use the menu below and follow these steps:
1. At the online menu, choose 4 (detailed setup).
2. At the detailed setup menu, choose 2 (configure field device variables).
3. At the configure field device variables menu, choose 1 (flow).
4. At the flow menu, choose 4 (flow damping).
5. Select the desired damping value.
6. Press F2 (send) to send the damping value to the flowmeter memory.
6.2.5
Flow direction
The configured flow direction (forward, reverse, or bi-directional) determines how flowmeter outputs 
and totalizers will react when fluid flows through the meter. The flow direction arrow on the meter is 
considered the "forward" flow direction, but the meter measures flow accurately in either direction.
To configure flow direction for the meter, use the menu below and follow these steps:
1. At the online menu, choose 4 (detailed setup).
2. At the detailed setup menu, choose 2 (configure field device variables).
3. At the configure field device variables menu, choose 1 (flow).
4. At the flow variables menu, choose 3 (flow direction), then choose the desired option. The 
table below lists how outputs and totalizers are affected by the option that is chosen.
5. To send the flow direction to the flowmeter, press F2 (send).
1 Process variables
2 Diag/service
3 Basic setup
4 DETAILED SETUP
5 Review
1 Flo unit
2 Flo cutoff
3 Flo direction
4 FLOW DAMPING
1 Charize sensor
2 CONFIG FLD 
DEV VAR
3 Config outputs
4 Device 
1 FLOW
2 Density
3 Temp unit
1 Process variables
2 Diag/service
3 Basic setup
4 DETAILED SETUP
5 Review
1 Flo unit
2 Flo cutoff
3 FLO DIRECTION
4 Flow damping
1 Charize sensor
2 CONFIG FLD 
DEV VAR
3 Config outputs
4 Device 
1 FLOW
2 Density
3 Temp unit
Table 6-1
Effect of flow direction on outputs and totalizers
Fluid flow 
direction
Output or 
totalizer
Flowmeter configuration
Forward
Reverse
Fluid flowing 
in same direction 
as flow arrow
on sensor
Milliamp output
Output increases as flow rate 
increases
Output goes to 3.8 mA
Pulse output
Output increases as flow rate 
increases
Output remains at 0 Hz
Internal totalizers
Flow totals increase
Flow totals remain constant
Fluid flowing 
in opposite direction 
from flow arrow 
on sensor
Milliamp output
Output goes to 3.8 mA
Output increases as flow rate 
increases
Pulse output
Output remains at 0 Hz
Output increases as flow rate 
increases
Internal totalizers
Flow totals remain constant
Flow totals increase