SMV 3000 Transmitter User’s Manual
1/99
152
A.3
Data Exchange Functions
Introduction
The exchange of data over the bi-directional data path between the
SMV 3000 transmitter and the PM/APM/HPM is based on imaging
SMV 3000 data through the use of Analog Input (AI) point parameters in
the STIMV IOP for each transmitter PV. This is done by mapping
parameters from the transmitter to the IOP, and from the IOP to the
transmitter as shown in Figure A-2.
While the mapped parameters are predefined in the IOP firmware, the
actual data exchange functions will depend on entries made during
STIMV IOP point building and transmitter PV selections made while
configuring the transmitter database through the SCT 3000
This section discusses various functions that affect how the data is
exchanged. Most of this information is for reference only, but some will
be helpful when making point building decisions. Refer to section 6 in the
PM/APM Smartline Transmitter Integration Manual for details about
STIMV IOP point building.
Figure A-2
Mapped Parameters are Basis for Data Exchange
Universal
Station
HM
NIM
PM/APM/HPM
FTA
STIMV
IOP
PMM
SMV 3000
Transmitter
with up to 4 PVs
SMV 3000 data
is mapped to
STIMV IOP
parameters.
AI point parameters
image SMV 3000 data
Continued on next page