SMV 3000 Transmitter User’s Manual 
1/99
5.2
Establishing Communications
Off-line Versus On-
line SMV
Configuration
The SCT 3000 allows you to perform both off-line and on-line
configuration of SMV transmitters.
 
Off-line configuration does not require connection to the transmitter.
By operating the SCT 3000 in the off-line mode, you can configure
database files of an unlimited number of transmitters prior to receipt,
save them either to hard disk or a floppy diskette, and then download
the database files to the transmitters during commissioning.
 
An on-line session requires that the SCT is connected to the transmitter
and allows you to download previously-configured database files at
any time during installation or commissioning of your field
application.  Note that you can also upload a transmitter’s existing
configuration and then make changes directly to that database.
Off-line Configuration
Procedures
Refer to the SCT User Manual (on-line) for detailed procedures on how to
off-line configure SMV transmitters using the SCT 3000.
SCT Hardware
Connections
A PC or laptop computer (host computer) which contains the SCT
software program, is connected to the wiring terminals of the SMV
transmitter and other smart field devices.  Figure 18 shows the hardware
components of the SCT.
Figure 18
SCT Hardware Components
PC Card
Commerically-available
Laptop or Desktop PC
SMARTLINE OPTION MODULE
Line Interface
Module
SCT Software Program running
on Windows 95, Windows 98 or
Windows NT Operating System
250 
Ω
 
Power
Supply
SMV 3000
23057
PRO
CES
S
Continued on next page