Honeywell SMV 3000 사용자 설명서

다운로드
페이지 217
1/99
SMV 3000 Transmitter User’s Manual
49
6.3
Configuring the SMV 3000 with The SCT
Using the SCT for
SMV 3000
Configuration
The SCT template files have tab cards that contain data fields for the SMV
parameters which you fill in.  You start with the Device tab card to enter
the device tag name (Tag ID) and other general descriptions.  Next, you
can select each tab card in order and configure each PV (PV1, secondary
variable if desired, PV2, PV3, and PV4).
  SMV Process Variable
SCT Template Tab Card
  PV1 (Differential Pressure)
DPConf
  PV2 (Absolute Pressure or 
APConf or GPConf  *
        Gauge Pressure) *
  PV3 (Process Temperature)
TempConf
  PV4 (Flow)
FlowConf
* PV2 will be AP of GP depending on SMV model
Use the Flow Compensation Wizard to setup the SMV 3000 for flow
applications.  The flow wizard guides you through the steps necessary to
complete your flow configuration.  See Subsection 6.10 and Appendix C
for more information about the flow wizard.
In the subsections below information is given for filling in some of the
SCT tab card data fields.  Supplementary background information and
reference data on SMV configuration that may be helpful is also
presented.  Use the SCT on-line help and user manual for detailed “how to
configure” information.
ATTENTION
If the transmitter detects an incomplete database upon power-up, it will
initialize the database parameters to default conditions. A setting or
selection with a superscript “d” in the following subsections identifies the
factory setting.