and 12" (30.5 cm) from the top. (Standard clearance.) If clearances 
stated on the heater differ from standard clearances, install water 
heater according to clearances stated on the heater.
Adequate clearance for servicing this appliance should be considered 
before installation, such as changing the anodes, etc.
A minimum clearance of 5" (12.7 cm) must be allowed for access 
to replaceable parts such as the thermostats, drain valve and relief 
valve.
When installing the heater, consideration must be given to proper 
location. Location selected should be as close to the wall as practicable 
and as centralized with the water piping system as possible.
FIGURE 4.
A gas water heater cannot operate properly without the correct amount 
of air for combustion.  Do not install in a confi ned area such as a closet, 
unless you provide air as shown in the “Locating The New Water 
Heater” section.  Never obstruct the fl ow of ventilation air.  If you have 
any doubts or questions at all, call your gas supplier.  Failure to provide 
the proper amount of combustion air can result in a fi re or explosion 
and cause death, serious bodily injury, or property damage.
FIGURE 5.
If this water heater will be used in beauty shops, barber shops, cleaning 
establishments, or self-service laundries with dry cleaning equipment, it 
is imperative that the water heater or water heaters be installed so that 
combustion and ventilation air be taken from outside these areas.  
Propellants of aerosol sprays and volatile compounds, (cleaners, 
chlorine based chemicals, refrigerants, etc.) in addition to being highly 
fl ammable in many cases, will also react to form corrosive hydrochloric 
acid when exposed to the combustion products of the water heater.  
The results can be hazardous, and also cause product failure.
INSULATION BLANKETS
Insulation blankets are available to the general public for external use 
on gas water heaters but are not necessary with these products.  The 
purpose of an insulation blanket is to reduce the standby heat loss 
encountered with storage tank heaters.  Your water heater meets or 
exceeds the National Appliance Energy Conversation Act standards 
with respect to insulation and standby loss requirements, making an 
insulation blanket unnecessary.
Should you choose to apply an insulation blanket to this heater, you 
should follow these instructions (For identifi cation of components 
mentioned below, see Figure 1).  Failure to follow these instructions 
can restrict the air fl ow required for proper combustion, potentially 
resulting in fi re, asphyxiation, serious personal injury or death.
• Do not apply insulation to the top of the water heater, as this will 
interfere with safe operation of the draft hood.
•  Do not cover the outer door, thermostat or temperature & pressure 
relief valve.
• Do not allow insulation to come within 2" (5.1 cm) of the fl oor  to 
prevent blockage of combustion air fl ow to the burner.
• Do not cover the instruction manual.  Keep it on the side of the 
water heater or nearby for future reference.
•  Do obtain new warning and instruction labels from the manufacturer 
for placement on the blanket directly over the existing labels.
• Do inspect the insulation blanket frequently to make certain it 
does not sag, thereby obstructing combustion air fl ow.
COMBUSTION AIR AND VENTILATION FOR 
APPLIANCES LOCATED IN UNCONFINED SPACES
UNCONFINED SPACE is space whose volume is not less than 
50 cubic feet per 1,000 Btu per hour (4.8 cubic meters per kW) of the 
aggregate input rating of all appliances installed in that space.  Rooms 
communicating directly with the space in which the appliances are 
installed, through openings not furnished with doors, are considered 
a part of the unconfi ned space.
In unconfi ned spaces in buildings, infi ltration may be adequate to 
provide air for combustion, ventilation and dilution of fl ue  gases.  
However, in buildings of tight construction (for example, weather 
stripping, heavily insulated, caulked, vapor barrier, etc.), additional air 
may need to be provided using the methods described in “Combustion 
Air and Ventilation for Appliances Located in Confi ned Spaces.”
COMBUSTION AIR AND VENTILATION FOR 
APPLIANCES LOCATED IN CONFINED SPACES
CONFINED SPACE is a space whose volume is less than 50 cubic 
feet per 1,000 Btu per hour (4.8 cm per kW)  of the aggregate input 
rating of all appliances installed in that space.