L4006,7,8; L6006,7,8 AQUASTAT
®
 CONTROLLERS
60-2104—10
8
INSTALLATION
When Installing This Product…
1. Read these instructions carefully. Failure to follow them 
could damage the product or cause a hazardous 
condition.
2. Check the ratings given in the instructions and on the 
product to make sure the product is suitable for your 
application.
3. Installer must be a trained, experienced service 
technician.
4. After installation is complete, check product operation as 
provided in these instructions.
WARNING
Explosion Hazard.
Can cause serious injury, death or property 
damage.
This product is intended for use only in systems with a 
pressure relief valve.
WARNING
Electrical Shock Hazard.
Can cause serious injury or death.
Disconnect power supply before beginning installation 
to prevent electrical shock or equipment damage.
CAUTION
Equipment Damage Hazard.
Use of incorrect device or improper installation can 
damage the system.
1. Do not replace immersion-type Aquastat Controller 
with strap-on Aquastat Controller.
2. Do not secure draw nut so tightly that retainer clamp 
can collapse tubing.
IMPORTANT
1. Terminals on these Aquastat relays are approved for 
copper wire only.
2. Controller may be used with or without immersion 
well. If used, well must snugly fit sensing bulb for best 
thermal response. Insert bulb until it rests against the 
bottom of the well. Use well of correct length and 
bend the tubing, if necessary, to provide enough force 
to hold the bulb against the bottom of the well. Avoid 
making a sharp bend in the tubing as it can produce a 
break in the tubing and cause loss of fill. This 
condition causes the High and Low Limit controls to 
be made continuously.
3. If well does not snugly fit on bulb, use the heat-
conductive compound, included with Super Tradeline 
and Tradeline models, as follows: Fold the plastic bag 
of compound lengthwise and twist gently. Snip the 
end of the bag and insert into the well. Slowly pull out 
the bag while squeezing firmly to distribute compound 
evenly in the well. Insert the bulb into the well. Bend 
the tubing, if necessary, to provide force to hold the 
bulb against the bottom of the well and to hold the 
outer end of the bulb firmly in contact with the side of 
the well. Wipe off excess compound.
The manufacturer usually provides a tapping for insertion of 
the controller sensing element. This tapping is located at a 
point where typical water temperature can be measured. 
Depending on the model, the element is inserted in an 
immersion well, through a boiler fitting, or directly immersed.
Installation should be made by a qualified service technician. 
Follow the instructions furnished by the system manufacturer, if 
available. Otherwise, refer to appropriate procedure listed 
below.
Mounting Immersion Well and Direct 
Immersion Models (L4006A,B,C,E,G; 
L4007A,B; L6006A,B; L6007A)
Installing Immersion Well Models 
(L4006A,B,E,G; L4007A,B; L6006A; L6007A)
On an existing installation, shut off the power and remove the 
old control. If the old immersion well appears suitable, and if 
the adapter clamp on the Aquastat Controller fits the old well 
spud, this well does not need to be replaced.
To replace the well:
1. If the system is filled, drain the system to a point below 
the boiler tapping.
2. Remove the old well from the boiler tapping.
3. Install the immersion well included with the controller. If 
the boiler tapping is greater than 1/2 in. (13 mm), use a 
reduction fitting to adapt the boiler opening to the 1/2 in. 
(13 mm) threads that are standard with the well or fitting. 
Fittings with 3/4 in. (19 mm) threads are also available.
4. Fill the system. Make sure that the well is screwed in 
tightly enough to prevent leakage. Do not use the case 
as a handle to tighten the well after the controller is 
secured to the well.
To install the controller:
1. Loosen the screw (at the top of the case, above the 
scale setting), and remove the cover. Loosen the two 
screws that secure the adapter clamp. (See Fig. 6).
2. Insert the sensing element into the immersion well.
3. Fasten the case of the Aquastat Controller to the well 
with the adapter clamp. Make certain that the clamp is 
properly positioned over the groove of the well spud. 
Also, be sure the flange at the opening of the well fits 
snugly into the opening of the case. The sensing bulb 
must bottom in the well.
NOTE: Some models include up to 3 in. (76 mm) extra capil-
lary tubing inside the case. In these models, pull out 
the extra tubing, if needed.