tank Cleanout proCedure
The  following  practices  will  ensure  longer  life  and  enable  the 
unit to operate at its designed efficiency:
1.  Once a month the heater should be flushed. Open the drain 
valve and allow two gallons of water to drain from the heater. 
Inlet water valve should remain open to maintain pressure in 
tank.
2.  A  cleanout  opening  is  provided  for  periodic  cleaning  of  the 
tank. Gas must be shut off and heater drained before opening 
cleanout.
To clean heater through cleanout opening, proceed as follows:
3.  Drain heater.
4.  remove outer cover plate from lower side of heater jacket.
5.  remove six (6) hex head screws securing tank cleanout plate 
and remove plate.
6.  remove lime, scale, or sediment using care not to damage 
the glass lining.
7.  Inspect  cleanout  plate  gasket,  if  new  gasket  is  required, 
replace with part no. 9004099215.
8.  Install  cleanout  plate.  Be  sure  to  draw  plate  up  tight  by 
tightening screws securely.
9.  replace outer jacket cover plate. 
In  some  water  areas  the  sediment  might  not  be  removed 
by  this  method  and  may  result  in  the  water  heater  making 
rumbling  or  boiling  noises.  To  dissolve  and  remove  these 
more  stubborn  mineral  deposits,  Un•lIMe  Professional 
Delimer should be used.
deliming using flo-jug method
Un•lIMe in the 5 gallon size is recommended for deliming of all 
models.  Contact  your  local  dealer,  distributor  or,  water  heater 
manufacturer.
Prepare the Water Heater
To  delime  the  water  heater  using  the  Flo-Jug  method,  first 
prepare the heater for deliming.
Explosion Hazard
Flammable hydrogen gases
may be present.
Keep all ignition sources away
from faucet when turning on
hot water.
Do not smoke or have open flame or sparks in vicinity of heater. 
Do not mix Un•lIMe with other chemicals. Do not allow contact 
with magnesium, aluminum or galvanized metals.
lime accumulation not only reduces the life of equipment but also 
reduces efficiency of the heater and increases fuel consumption.
The usage of water softening equipment greatly reduces the hardness 
of the water. however, this equipment does not always remove all of 
the hardness (lime). For this reason it is recommended that a regular 
schedule for deliming be maintained.
The  time  between  cleaning  will  vary  from  weeks  to  months 
depending upon water conditions and usage.
The depth of lime buildup should be measured periodically. heaters 
equipped with cleanouts will have about 2" of lime buildup when 
the level of lime has reached the bottom of the cleanout opening. A 
schedule for deliming should then be set up,based on the amount 
of time it would take for a 1" buildup of lime. It is recommended that 
the water heater initially be inspected after 6 months.
example 1:
Initial inspection after 6 months shows 1/2" of lime accumulation. 
Therefore, the heater should be delimed once a year.
example 2:
Initial inspection after 6 months shows 2" of lime accumulation. 
Therefore, the heater should be delimed every 3 months.
figure 28.
deliming solVents
Un•lIMe is recommended for deliming.  Un•lIMe is a patented 
food grade acid which is safe to handle and does not create the 
harmful fumes which are associated with other products.
Un•lIMe may be obtained from your dealer, distributor or water heater 
manufacturer. Order Part number 9005416105, 1 gallon, packed 4 
gallons per case or Part number 9005417105, 5 gallon  container.
nOTe: Un•lime is not available for use in Canada.
hydrochloric base acids are not recommended for use on glass 
lined tanks.
Observe handling instructions on label of product being used.