no  valve  or  other  obstruction  is  to  be  placed  between  the 
Temperature-Pressure relief Valve and the tank. Do not connect 
discharge  piping  directly  to  the  drain  unless  a  6”  (15.2  cm) 
air  gap  is  provided.  To  prevent  bodily  injury,  hazard  to  life,  or 
property damage, the relief valve must be allowed to discharge 
water in adequate quantities should circumstances demand. If 
the discharge pipe is not connected to a drain or other suitable 
means, the water flow may cause property damage.
Water Damage Hazard
Temperature-Pressure Relief Valve discharge
pipe must terminate at adequate drain.
CAUTION
t&p Valve discharge pipe requirements:
•  Shall not be smaller in size than the outlet pipe size of the 
valve, or have any reducing couplings or other restrictions.
•  Shall not be plugged or blocked.
•  Shall not be exposed to freezing temperatures.
•  Shall be of material listed for hot water distribution.
•  Shall be installed so as to allow complete drainage of both 
the Temperature-Pressure relief Valve and the discharge 
pipe.
•  Must terminate a maximum of six inches above a floor 
drain or external to the building. In cold climates, it is 
recommended that the discharge pipe be terminated at an 
adequate drain inside the building.
•  Shall not have any valve or other obstruction between the 
relief valve and the drain.
Burn hazard.
Hot water discharge.
Keep clear of Temperature-
Pressure Relief Valve
discharge outlet.
The  Temperature-Pressure  relief  Valve  must  be  manually 
operated  at  least  twice  a  year.  Caution  should  be  taken  to 
ensure that (1) no one is in front of or around the outlet of the 
Temperature-Pressure  relief  Valve  discharge  line,  and  (2)  the 
water  manually  discharged  will  not  cause  any  bodily  injury  or 
property  damage  because  the  water  may  be  extremely  hot.  If 
after  manually  operating  the  valve,  it  fails  to  completely  reset 
and continues to release water, immediately close the cold water 
inlet to the water heater, follow the draining instructions in this 
manual, and replace the Temperature-Pressure relief Valve with 
a properly rated/sized new one.
note: The purpose of a Temperature-Pressure relief Valve is 
to prevent excessive temperatures and pressures in the storage 
tank.  The  T&P  valve  is  not  intended  for  the  constant  relief  of 
thermal expansion. A properly sized thermal expansion tank must 
be installed on all closed systems to control thermal expansion, 
see Closed Water Systems and Thermal expansion on page 13.
If you do not understand these instructions or have any questions 
regarding the Temperature-Pressure relief Valve call the toll free 
number  listed  on  the  back  cover  of  this  manual  for  technical 
assistance.
ComBustiBle material storage
Fire or Explosion Hazard
Read instruction manual before
installing, using or servicing
water heater.
Avoid all ignition sources if you smell gas.
Do not store or use gasoline or other flammable vapors and
liquids in the vicinity of this or any other appliance.
Use only the gas shown on the water heater rating label.
Keep ignition sources away from faucets after extended
periods of non-use.
Maintain required clearances to combustibles.
Do not expose water heater controls to excessive gas
pressure.
Keep water heater area clear and free of combustible materials, 
gasoline and other flammable vapors and liquids.
Contaminated air
Breathing Hazard - Carbon Monoxide Gas
Install water heater in accordance with
the Instruction Manual and NFPA 54 or
CAN/CSA-B149.1.
To avoid injury, combustion and ventilation
air must be taken from outdoors.
Do not place chemical vapor  emitting
products near water heater.
Breathing carbon monoxide can cause brain damage or
death. Always read and understand instruction manual.
Corrosion of the flue ways and vent system may occur if air for 
combustion  contains  certain  chemical  vapors.  Such  corrosion 
may result in failure and risk of asphyxiation.
Combustion air that is contaminated can greatly diminish the life 
span of the water heater and water heater components such as 
hot surface igniters and burners. Propellants of aerosol sprays, 
beauty shop supplies, water softener chemicals and chemicals 
used in dry cleaning processes that are present in the combustion, 
ventilation or ambient air can cause such damage.
Do not store products of this sort near the water heater. Air which 
is brought in contact with the water heater should not contain any 
of these chemicals. If necessary, uncontaminated air should be 
obtained from remote or outdoor sources. The limited warranty 
is  voided  when  failure  of  water  heater  is  due  to  a  corrosive 
atmosphere.  (See  limited  warranty  for  complete  terms  and 
conditions).