the eliminator (self-cleaning system)
These  units  include  The  eliminator  (Self-Cleaning  System) 
installed in the front water inlet, See figure 1. The eliminator inlet 
tube can only be used in the front water inlet connection. Do not 
install the eliminator inlet tube in either the top or back inlet water 
connection. The eliminator must be oriented correctly for proper 
function. There is a marked range on the pipe nipple portion of 
the eliminator, that must be aligned with the top of the inlet spud. 
A label above the jacket hole has an arrow that will point to the 
marked portion of the pipe nipple if the orientation is correct. if the 
arrow does not point within the marked range on the pipe nipple, 
adjust the pipe nipple to correct. A pipe union is supplied with the 
eliminator to reduce the probability of misaligning the eliminator 
accidentally  while  tightening  the  connection  to  the  inlet  water 
supply line. improper orientation of the eliminator can cause poor 
performance of the heater and can significantly reduce outlet water 
temperatures during heavy draws.
note: the eliminator may have 1, 3 or 7 cross tubes.
figure 1.
high limit switch
The digital thermostat (figure 2) contains the high limit (energy 
cutoff) switch. The high limit switch interrupts main burner gas 
flow should the water temperature reach 203°f (95°C).
in the event of high limit switch operation, the appliance cannot 
be  restarted  unless  the  water  temperature  is  reduced  to 
approximately 120°f (49°C). The high limit reset button on the 
front of the control then needs to be depressed.
Continued  manual  resetting  of  high  limit  control,  preceded  by 
higher  than  usual  water  temperature  is  evidence  of  high  limit 
switch operation. The following is a possible reason for high limit 
switch operation:
•  A malfunction in the thermostatic controls would allow the gas 
valve to remain open causing water temperature to exceed the 
thermostat setting. The water temperature would continue to 
rise until high limit switch operation.
Contact your dealer or service agent if continued high limit switch 
operation occurs.
digital thermostat
figure  2.
electronic ignition control
each heater is equipped with a ignition module. The solid state 
ignition control (figure 3), ignites the main burner by utilizing a 
silicon nitride igniter. The silicon nitride igniter shuts off during 
the heating cycle and the main burner flame is sensed through 
a  remote  flame  sensor  integral  to  the  silicon  nitride  igniter 
assembly.
The ignition control will try to ignite the main burner three times 
before lockout. Then it waits one hour before trying again to ignite 
the main burners. This is a continuous cycle.
ignition control Board
figure 3.
exhaust inducer (Blower assy.)
All models are equipped with an exhaust inducer. The inducer 
assists in drawing in fresh air to the unit for combustion and then 
assists in dispensing the combustion by-products into the venting 
leading outside.
The exhaust inducer is equipped with a gravity controlled damper 
to reduce the amount of heat loss through the flue, improving   
efficiency.
exhaust inducer
figure 4.
uncrating
The  heater  is  shipped  with  the  inducer  already  installed. The 
wiring  conduit  runs  from  the  thermostat  to  the  inducer.  Before 
turning unit on, check to make sure the wiring conduit is securely 
plugged into the inducer.
low gas pressure switch
The Low Gas Pressure Switch monitors the gas supply pressure. 
if the gas supply pressure drops below 5.2” W.C., the burners are 
extinguished (if the heater is running) or the heater will not start up.