Application – Three-Phase Motors
Applications
SubMonitor is designed to protect 3-phase pumps/
motors with service factor amp ratings (SFA) from 5 
to 350 A (approx. 3 to 200 hp). Current, voltage, and 
motor temperature are monitored using all three legs 
and allows the user to set up the SubMonitor quickly 
and easily.
Protects Against
• Under/Overload
• Under/Overvoltage
• Current Unbalance
• Overheated Motor 
    (if equipped with Subtrol Heat Sensor)
• False Start (Chattering)
• Phase Reversal
In some installations, power supply limitations make it 
necessary or desirable to increase the power factor of a 
submersible motor. The table lists the capacitive kVAR 
required to increase the power factor of large Franklin 
three-phase submersible motors to the approximate 
values shown at maximum input loading.
Capacitors must be connected on the line side of the 
overload relay, or overload protection will be lost.
Values listed are total required (not per phase).
Table 31 kVAR Required 60 Hz
MOTOR
KVAR REQUIRED FOR PF OF:
HP
KW
0.90
0.95
1.00
5
3.7
1.2
2.1
4.0
7.5
5.5
1.7
3.1
6.0
10
7.5
1.5
3.3
7.0
15
11
2.2
4.7
10.0
20
15
1.7
5.0
12.0
25
18.5
2.1
6.2
15.0
30
22
2.5
7.4
18.0
40
30
4.5
11.0
24.0
50
37
7.1
15.0
32.0
60
45
8.4
18.0
38.0
75
55
6.3
18.0
43.0
100
75
11.0
27.0
60.0
125
90
17.0
36.0
77.0
150
110
20.0
42.0
90.0
175
130
9.6
36.0
93.0
200
150
16.0
46.0
110.0
SubMonitor Three-Phase Protection
Power Factor Correction
31