Test Record
Date
By
Amp Setting
Time Setting
Notes
Informational Charts
PERFORMANCE TEST REPORT 
GROUND FAULT PROTECTION
Job: ______________________________________________________________________________________________________________
Location:______________________________________________________   Date of Test: _______________________________________
Circuit:_____________________________________________________________________________________________________________
Switchboard: _________________________________________________________________________Single/Double End _____________
Disconnect Device: _________________________________________________________________________________________________
GF Protective Device: _______________________________________________________________________________________________
GF Sensor: ________________________________________________________________________________________________________
Test Equipment: (Describe on back or attach a page.)
Test Setup and Method:  (Describe on back or attach a page.)
Disconnect
Device
Main Bonding
Jumper
Neutral Disconnect
Link
No grounds permitted
downstream from
bonding jumper
neutral, if used
From Sensor
To Control Power Source
Lo
a
d
Main P
ower
 S
ource
Ground
Fault
Relay (GFR)
Shunt
Trip
Device
To GFR
To GFR
#2
#1
Fig. #1
S
e
nsor
 (GFS)
S
e
nsor
 (GFS)
Ground Fault Testing
Warning:
The following should be performed only by qualified personnel as defined in N.E.C. Article 100. The ground fault sensor (GFS), ground fault
relay (GFR), must be installed as in Fig. 1.
GFS #1, is the standard location
GFS #2, alternate location for GFS
1. Disconnect Main Power Source.
2. Remove the neutral disconnect link. Make sure the neutral is
grounded only by the main bonding jumper, which must be on 
the line side of the sensor.
3. Close all branch devices.
4. Using a “megger” type meter, measure the resistance of the load
phase and neutral to ground. This is to ensure that no ground
connections exist in the system. Resistance readings of (1)
Megohm or greater are preferred.
5. Re-install the neutral disconnect link.
6. Open all branch devices.
7. Connect the main power source.
8. To Test The Entire System.
a. Check for control power. (LED should be illuminated).
b. Press the “push to test” switch on the relay.
c. The trip indicator should go to the “tripped” position and the
disconnect device should operate.
d. Release the “push to test” switch and return the trip indicator to
the “reset” position.
e. Reset or “close” the disconnect device for normal operation of 
the switchboard.
9. This test meets the requirements of the National Electrical Code 
Section 230.95 (C).
11.5 Ground Fault Test Record- External