Cooper Bussmann DCM 433 사용자 설명서

다운로드
페이지 7
CF 26 
4/2001 
Specifications 
NOTE: Unless otherwise noted, specifications apply after one hour warm up at 25°C ambient. Temperature 
coefficients apply between 0°C and 55°C ambient. 
 
Isolation 
 
Input to Output 
700 VDC 
60pF 
Amplifier 
Gain 
 Adjustment 
Range 
 
Input 4-20mA Output 
5 mV to 50 mV 
        Linearity 
±0.01% of Full Scale 
        Temperature Stability 
50 PPM (0.005%/°C) 
Input Noise 
 
.1 Hz to 10 Hz 
2µV P-P 
Tare Adjustment Range 
 Bridge 
Offset 
-3 mV to +25 mV  
(Equals 80% F.S. of 3 mV/V cell) 
Input Resistance 
 
Differential and Common Mode 
1000 megaohm 
Common Mode Rejection, DC 
100 dB minimum 
Common Mode Input 
+5 Volts 
Output 
0 or 4 mA 
Zero Adjust 
 Temperature 
Coefficient 
1 µA/°C 
Current Output Span 
4 to 20 mA or 0 to 20 mA 
 
Compliance Voltage 
-1 to +20 Volts 
 
Current 
-1 mA to +20 mA 
 
Loop Resistance 
0 to 1000 ohms 
 
Frequency Response, -3dB 
10 Hertz, 2 Pole Roll Off 
 Response 
Time 
 
Rise Time 10% to 90% 
 
To 0.1% of Final Value 
 
35 ms 
100 ms 
Bridge Supply 
Voltage Adjustment Range 
5 to 10 Volts 
 
Temperature Coefficient 
100 PPM Typical 
 Fixed 
10.2V 
±2.5% 
 
Temperature Coefficient 
60 PPM Typical 
Load Current 
0 to 120 mA 
Regulation - Load and Line 
0.02% maximum 
Output Noise 
 
120 Hz Bandwidth 
1 mV RMS, Maximum 
Power Input 
115 VAC, ±10V 50/60 Hz @7 VA 
 
Optional 
220 or 230 VAC, ±10% 
Line Isolation 
 Capacitance 
60 
pF 
 
Dielectric Withstand 
1100 Volts RMS 
Environment 
 
Ambient Operating 
-25°C to +55°C 
 
Storage 
-25°C to +85°C 
Weight 
18 oz. (510 grams) 
Size 
3.75” L x 2.0” W x 2.87” H 