**Effective Intensity Requirements for Sleeping Area
Visible Notification Appliance
Distance from Ceiling to Top of Lens
Intensity
greater than or equal to 24"
110 Cd
less than 24"
177 Cd
IV.    MOUNTING ROUGH-IN BOX AND RUN WIRING     
MOUNTING OPTIONS
All models shown with optional strobe.
SYSTEM CONSIDERATIONS
1.   To select the proper wattage input for the speaker.  Move the jumper to the appropriate pin.  
Refer to Section VII for the proper terminal.
2.   Always maintain electrical isolation between speaker and strobe wiring on combination units.
3.   Do not exceed 130% of rated speaker voltage.  If excessive distortion is heard, check 
amplifier for signal clipping.  If clipping exists, reduce either amplifier input or gain.
4.   When extension rings are used, the conduit should always enter through the backbox.
CAUTION
WHEN INSTALLING, ROUTE FIELD WIRING AWAY FROM SHARP
PROJECTIONS, CORNERS AND INTERNAL COMPONENTS.
NOTE:  Strobes are not recommended for use on coded or pulsing signaling circuits. 
PANEL VOLTAGE - DEVICE MINIMUM VOLTAGE
TOTAL CURRENT DRAW
* INCLUDES WIRE TO AND FROM APPLIANCE.
ASSUMES ALL APPLIANCES ARE AT THE END OF WIRE RUN (WORST CASE).
CAUTION:  APPLIES ONLY TO REGULATED SUPPLIES. 
V.     CHECKOUT AND TROUBLESHOOTING
1.  Supply power to the system control panel.  The auxiliary signaling device should not be 
activated. 
2.  If the signal is activated:
a.  Check all smoke and fire detectors in the system to make sure they have not been 
activated.
b.  Check all wiring connections to make sure the signal detection circuits are not reversed or 
shorted together.  Check wire color codes and traces.
3.  To test the "SPKE" series and other signaling appliances, trip the auxiliary panel or activate 
alarm circuit at the main control panel or activate one of the fire detection units in the system.  
All auxiliary signals should be activated.
4.  An operational test on this product should be conducted in accordance with National Standards 
or at a minimum annually and more often if dictated by local and state codes or authorities 
having jurisdiction.
SIGNALING APPLIANCE LIMITATIONS:
Your speaker meets or exceeds current audibility requirements of Underwriters Laboratories.  
However, if the appliance is located outside a bedroom it may not wake up a sound sleeper, 
especially if the room door is closed or only partially open.
WARNING
THIS APPLIANCE WILL NOT OPERATE WITHOUT ELECTRICAL POWER.  AS
FIRES FREQUENTLY CAUSE POWER INTERRUPTIONS, GENTEX SUGGESTS
YOU DISCUSS FURTHER SAFEGUARDS WITH YOUR LOCAL FIRE 
PROTECTION SPECIALIST.
VI.    TO RETURN A UNIT
Should you experience problems with your "SPKE" unit, proceed as follows:
1.  Turn off electrical power to the auxiliary alarm circuit.
2.  Unscrew the unit from the mounting box.
3.  Disconnect the unit from the field wiring.  Reconnect the two positive supply voltage circuits 
(red wires) and the two negative supply voltage circuits (black wires) of the auxiliary alarm 
circuit to maintain power to the other auxiliary alarm appliances in the system. 
4.  Carefully pack the defective unit (the manufacturer cannot be responsible for consequential 
damage due to shipping or mishandling).  Include your return address and complete details as 
to the nature of the difficulties being experienced and date of installation.
5.  Return to: Gentex Corporation, 10985 Chicago Drive, Zeeland, MI  49464.  Prior to returning, 
call Gentex @ 1-800-436-8391 to obtain an RMA number from our return department.
NOTE: DO NOT USE
LOOPED WIRE UNDER 
TERMINALS.  BREAK WIRE
RUN TO PROVIDE 
SUPERVISION OF 
CONNECTION.
*MAX. WIRE DISTANCE (IN FEET) = 
X WIRE CONDUCTIVITY (STROBE ONLY)