Installing the Vehicle Imaging Subsystem 
29 
VIS-CAM System 
Figure 25.  Two lane controller. 
 
3.4 Illumination Options 
3.4.1  Installing the TNF-31 Flash 
The connection to the Flash unit in the VIS CAM 300 is shown in Table 9 and Figure 26. 
Figure 26.  TNF-31 flash unit 
 
 
Table 9 
Flash unit connection in VIS CAM 400. 
Pin Signal 
Description 
Connection 
to 
I/O Gnd  IO Board Gnd 
Pin 2 when no power is available from the flash 
Gnd 
Flash Gnd 
Flash ground (negative power terminal) 
Out 
Strobe out 
Strobe input on flash unit 
4 Stat 
Strobe 
status 
Status output from flash unit 
5 FPWR Flash 
power 
Power from flash to output circuit on I/O Board 
6 24V 
IO board 24V (Fused0.5A) 
Pin 5 when no power is available from the flash 
 
The cable from the flash unit is connected to the VIS CAM 300 I/O Board as shown in figure 3.17 and 
3.18. There are two examples shown: one where the output circuit on the I/O Board is powered 
from the flash unit and one where the output circuit is powered from the I/O Board. 
It is recommended that I/O Board output circuit be powered from the flash unit in order to obtain 
galvanic isolation between the to units. In cases where this is not possible (such as when using mains 
supplied flash units) power is taken from the I/O Board. 
The cable must be shielded and the shield connected to the metal at the cable entry in the camera 
house. The switch labelled S3 on the VIS CAM 300 I/O Board must be in position “NIGHT L” (away 
from connector X5 as shown below).