CLSFY-PT (Call Classifier Port) 
9
Tone Detection Verification Test (#42)
This test checks the operation of the TN744 in touch-tone receiver, call classifier 
and R2-MFC modes. It verifies the circuit pack’s ability to detect DTMF, ring 
back, busy reorder and modem answer tones and to generate and detect 
forward and backward MFC tones.
Table 9-172.
TEST #42 Tone Detection Verification Test
Error 
Code
Test 
Result
Description/ Recommendation
none
ABORT
The system was not able to allocate all the resources needed for this test 
OR there was an internal system error.
1
ABORT
The system could not allocate all the resources needed to test the tones.
1001
ABORT
The system was unable to put the call classifier port in the appropriate 
mode to test it.
1002
ABORT
The system could not allocate time slots for the test connection. This 
situation could occur when the system is heavily loaded. If the system is not 
heavily loaded, then test the TDM-BUS via the test tdm command. 
1. Retry the command at 1-minute intervals for a maximum of 5 times.
1003
ABORT
The system could not allocate a Tone-Clock for the test connection. This 
may be caused by a heavy load on the system or by a faulted Tone-Clock.
1. Check to see if there are any alarms against the Tone-Clock in the port 
network where the test aborted. If so refer to the recommended 
procedures for TONE-BD or TONE-PT.
2. If a new Tone-Clock has been inserted, allow about 1-minute for 
maintenance to run on the newly inserted circuit pack.
3. Retry the command at 1-minute intervals for a maximum of 5 times.
2000
ABORT
Call classifier circuit pack’s response to the test request was not received 
within the allowable time period.
1. Retry the command at 1-minute intervals for a maximum of 5 times.
2006
ABORT
Indicates that the active Tone-Clock circuit pack or a Tone Detector circuit 
pack may not be functioning properly. 
1. Test the 
active Tone-Clock circuit pack in the port network with the test 
tone-clock UUC command and refer to the TONE-BD section for 
failures.
2. Retry the command at 1-minute intervals for a maximum of 5 times.
2100
ABORT
Could not allocate the necessary system resources to run this test.
1. Retry the command at 1-minute intervals for a maximum of 5 times.