Install and Wire Telephones and Other Equipment
Page 5-63
Multi-point Adapters
5
Basic Multipoint Installation Distances
Figure 5-28
provides cabling information for fan-out of ISDN-BRI multi-point
installations. The terminating resistor is generally located in the satellite closet. All
distances assume 24 AWG (#5) (0.26 mm
distances assume 24 AWG (#5) (0.26 mm
2
) D-Inside Wire (DIW).
Figure 5-28.
Basic Multi-point with 1 Work Location
Figure Notes
1. S-Interface Source (TN556)
2. Terminating Resistor
3. Satellite Closet
4. Maximum Distance from S-Interface
Source to Work Location (1600 Feet)
(488 m)
(488 m)
5. Maximum Distance From Satellite
Closet to Work Location (250 Feet)
(76 m)
(76 m)
6. System Cabinet
7. Terminating Endpoint 1
8. Terminating Endpoint 2
9. Work Location
10. Maximum Distance from
Information Outlet to Terminating
Endpoint (33 Feet) (10 m)
Endpoint (33 Feet) (10 m)
11. Information Outlet (Bridged Tap)